12.3 b: Application
b2-08: Magnetic Flux Compensation Value
No.
Name
(Hex.)
b2-08
Magnetic Flux
Compensation Value
(0190)
This parameter is effective when you start a high-capacity motor (a motor with a large secondary circuit time
constant). This function can quickly increase motor flux to make high starting torque (a process called initial
excitation).
The current level for DC Injection Braking at start changes linearly from the setting of b2-08 to the setting of b2-
03 as shown in
Figure
12.21.
Note:
• If b2-08 < 100%, flux will develop very slowly.
• When b2-08 = 0%, the DC current level will be the DC Injection current set in b2-02 [DC Injection Braking Current].
• If b2-08 is set too high, DC Injection Braking at start can cause a large noise. Adjust b2-08 to decrease the volume to the permitted
level.
b2-12: Short Circuit Brake Time @ Start
No.
Name
(Hex.)
b2-12
Short Circuit Brake Time @
Start
(01BA)
This function stops and restarts a coasting PM motor. The drive short circuits all the three motor phases to make
braking torque in the motor.
Set this parameter to 0.00 to disable the function.
Note:
• Short circuit Braking will let external forces rotate the PM motor. Use DC Injection Braking to prevent motor rotation from external
forces.
• Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
b2-13: Short Circuit Brake Time @ Stop
No.
Name
(Hex.)
b2-13
Short Circuit Brake Time @
Stop
(01BB)
This function fully stops a PM motor with a large inertia during deceleration and will not let the inertia continue to
rotate the motor.
Short Circuit Braking operates for the time set in b2-13 when output frequency is less than the value set in b2-01
[DC Injection/Zero SpeedThreshold] or E1-09 [Minimum Output Frequency].
Set this parameter to 0.00 to disable the function.
Note:
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
488
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial
Excitation) as a percentage of E2-03 [Motor No-Load Current].
Figure 12.21 DC Current Level during DC Injection Braking at Start
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking time at start.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking time at stop.
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
0%
(0 - 1000%)
Default
(Range)
0.00 s
(0.00 - 25.50 s)
Default
(Range)
A1-02 = 8: 0.00 s
Other than A1-02 = 8: 0.50
s
(0.00 - 25.50 s)