YASKAWA CIPR-GA50C series Technical Manual page 621

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

Setting Value
66
Comparator1
67
Comparator2
69
External Power 24V Supply
6A
Data Logger Error
*1
Inverse output is not available.
Extend MFDO1 to MFDO3 Function Selection
You can set MFDO functions to bit 0 to bit 2 [MEMOBUS MFDO1 to 3] of MEMOBUS register 15E0 (Hex.).
Use H2-40 to H2-42 [Mbus Reg 15E0h bit0 to bit2 Output Func] to select the function.
Figure 12.73 Functional Block Diagram of MEMOBUS Multi-function Output
Register No.
(Hex.)
15E0
Note:
• Refer to H2-xx "MFDO Setting Values" for more information about MFDO setting values.
• When you do not set functions to H2-40 to H2-42, set them to F.
Output of Logical Operation Results of MFDO
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use H2-60, H2-63, and H2-66 [Term MA,MB,MC Secondary Function, Terminal P1 Secondary Function, and
Terminal P2 Secondary Function] to set the function of the output signal for which you will perform logical
operations.
Use H2-61, H2-64, and H2-67 [Term MA,MB,MC Logical Operation, Terminal P1 Logical Operation, and
Terminal P2 Logical Operation] to set the logical operation.
Figure 12.74 Functional Block Diagram of Logical Operation Output for MFDO 1
Logical Operation Selection
H2-61, H2-64, H2-67
0
1
2
3
4
YASKAWA SIEPC71061753A GA500 Technical Manual
Function
Reference
640
640
641
641
Table 12.62 MEMOBUS MFDO Registers
Table 12.63 MFDO Logical Operation Table
Logical Operation Expression
A=B=1
A=1 or B=1
A=0 or B=0
A=B=0
12.8 H: Terminal Function Selection
Setting Value
90 - 92
DWEZ Digital Output 1 to 3
Inverse output of 0 to 92
Sets an inverse output of the function for
the MFDO. Put a 1 at the front of the
100 - 192
function setting to set inverse output. For
example, set 138 for inverse output of 38
[Drive Enabled].
Name
bit0
MEMOBUS MFDO 1
bit1
MEMOBUS MFDO 2
bit2
MEMOBUS MFDO 3
A=B
Function
Reference
641
641
Logical Operation Notation
A=B
12
621