12.2 A: Initialization Parameters
• Set Related Parameters
Table 12.20
shows examples of parameter settings to use the terminal P2-C2 as the holding brake open and
close signal.
Brake Open and Close Signal
Signal Name
L4-07 = 0
Frequency (FOUT) Detection 2
H2-03 = 5
*1
When A1-02 = 2 [Open Loop Vector], it is the usual setting range. When A1-02 = 0 [V/f Control], set L4-01 to the rated slip
frequency of the motor + approximately 0.5 Hz. If you set the value too low, motor torque will not be sufficient and it will cause
motor rollback. Set the parameter to agree with these conditions at the same time. If you set the value too high, it will cause
overshoot at start.
• L4-01 > E1-09 [Minimum Output Frequency]
• L4-01 > L4-02 [Speed Agree Detection Width]
*2
Use L4-02 to adjust the detection width of Frequency Detection 2. If rollback occurs when the motor stops, change the frequency to
approximately 0.1 Hz.
Sequence Circuit Configuration
Use these conditions to set the circuit for the open/close sequence of the holding brake:
• Set the sequence-side operation conditions to activate terminal P2-C2 and open the holding brake.
• Set the sequence to close the holding brake in an emergency if the drive detects a fault.
• Set the sequence to open the holding brake when you enter an increase or decrease command.
*1
L4-07 = 0 [Speed Agree Detection Selection = No detection during baseblock]
Time Chart
Figure 12.3
shows the open and close sequence of the holding brake.
Figure 12.3 Holding Brake Open and Close Sequence Time Chart (V/f, OLV)
468
Table 12.20 Holding Brake Open and Close Signal Setting Example
Parameter Settings
Speed Agree Detection Level
Speed Agree Detection Width
Figure 12.1 Frequency Detection 2
Figure 12.2 Sequence Circuit Configuration Diagram
Brake Open and Close Level Adjust
Signal Name
Parameter Settings
L4-01 = 1.0 Hz to 3.0 Hz
L4-02 = 0.0 Hz to 0.5 Hz