C2: S-Curve Characteristics - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

Figure 12.39 Example 2: Acceleration/Deceleration Rate (When C1-14 = 40 Hz, E1-04 = 60 Hz, and the Frequency
Figure 12.40 Example 3: Acceleration/Deceleration Rate (When C1-14 = 80 Hz, E1-04 = 60 Hz, and the Frequency
Note:
Figure 12.38
to
Figure 12.40
• When L3-01 ≠ 0 [Stall Prevention during Accel≠ Disabled], Stall Prevention could cause the acceleration time to be longer than the set
value.
• When L3-04 ≠ 0 [Stall Prevention during Decel ≠ Disabled], Stall Prevention could cause the deceleration time to be longer than the
set value.

C2: S-Curve Characteristics

Use S-curve characteristics to smooth acceleration and deceleration and to minimize abrupt shock to the load.
Set S-curve characteristic time during acceleration/deceleration at start and acceleration/deceleration at stop.
The following figure explains how S-curves are applied.
Figure 12.41 S-Curve Timing Diagram - Forward/Reverse Operation
Note:
• If STPo [Motor Step-Out Detected] occurs when starting a PM motor, try increasing the value set to C2-01.
• Setting the S-curve will increase the acceleration and deceleration times.
YASKAWA SIEPC71061753A GA500 Technical Manual
Reference is 60 Hz)
Reference is 60 Hz)
show the accel/decel times when C2-01 to C2-04 [S-Curve Times @ Start/End of Accel/Decel] = 0.00 s.
12.4 C: Tuning
12
525

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents