Note:
• You can set this parameter when C6-02 = B [Carrier Frequency Selection = Leakage Current Detection Reduction Rate PWM].
• When the setting value increases, the current monitor will start up slowly. Examine the relevant sequence for problems.
If errors occur in the values on the current monitor during acceleration/deceleration, increase the setting value.

L2: Power Loss Ride Through

L2 parameters set the drive operation during momentary power loss and the KEB Ride-Thru function method of
operation.
KEB Ride-Thru Function
KEB is an acronym for Kinetic Energy Backup. If the drive detects a power loss or momentary power loss, it will
quickly decelerate the motor. The drive uses regenerative energy from the motor to keep the main circuit
operating. When you return power during motor deceleration, the drive returns operation to the status before the
power loss. The KEB Ride-Thru function is different than other functions for continuous operation. If the drive
detects momentary power loss, the motor will ramp to stop. It will not coast to stop. This function is applicable for
applications in which it is necessary to prevent materials from running out, for example control for film and fiber
lines.
The KEB Ride-Thru function has 4 methods of operation. Parameter L2-29 [Kinetic Energy Backup Method] sets
the method.
When you use the KEB Ride-Thru function with one drive, set L2-29 = 0, 1 [Single Drive KEB Ride-Thru 1,
Single Drive KEB Ride-Thru 2].
If deceleration in coordination with more than one drive is necessary, for example textile machinery line systems,
set L2-29 = 2, 3 [System KEB Ride-Thru 1, System KEB Ride-Thru 2].
Kinetic Energy
L2-29
Backup Method
0
Single Drive KEB
The drive uses regenerative energy from the motor to keep the DC bus
Ride-Thru 1
voltage at the level set in L2-11 [KEB DC Bus Voltage Setpoint] while
it adjusts the rate of deceleration.
The KEB operation continues while the drive adjusts the deceleration
rate with the setting of C1-09 [Fast Stop Time].
1
Single Drive KEB
The drive uses information about the inertia of the connected
Ride-Thru 2
machinery to find the deceleration rate necessary to keep the DC bus
voltage at the level set in parameter L2-11.
The drive uses system inertia to calculate the deceleration time. You
cannot adjust this value.
2
System KEB Ride-
The drive does not monitor the DC bus voltage. The drive decelerates
Thru 1
at the KEB deceleration time set in L2-06.
Use L2-06 to set the time necessary to decelerate from the current
frequency reference to 0 Hz. More than one drive can decelerate and
keep a constant speed ratio between drives.
3
System KEB Ride-
The drive uses the KEB deceleration time set in L2-06 to decelerate
Thru 2
and it also monitors the DC bus voltage.
If the voltage level increases, the drive momentarily holds the
frequency to prevent an ov before it continues to decelerate.
KEB Ride Thru Start
When L2-01 = 3, 4, 5 [Power Loss Ride Through Select = Kinetic Energy Backup: L2-02, Kinetic Energy
Backup: CPU Power, Kinetic Energy Backup: DecelStop], the drive starts the KEB operation immediately after it
detects a momentary power loss. When one of these conditions occur, the drive will activate KEB Ride-Thru:
• KEB Ride-Thru 1 set for the MFDI terminal becomes enabled (terminal is deactivated when H1-xx = 65 or
terminal is activated when H1-xx = 66).
The drive uses the mode selected L2-29 [Kinetic Energy Backup Method] to start KEB operation.
• KEB Ride-Thru 2 set for the MFDI terminal becomes enabled (terminal is deactivated when H1-xx = 7A or
terminal is activated when H1-xx = 7B).
The drive automatically starts Single KEB Ride-Thru 2 and it ignores the setting of L2-29.
• The DC bus voltage is less than the level set in L2-05 [Undervoltage Detection Lvl (Uv1)].
The KEB operation will start as specified in L2-29.
Note:
If you try to set KEB Ride-Thru 1 and 2 to the MFDI terminals at the same time, it will trigger oPE03 [Multi-Function Input Setting
Err].
YASKAWA SIEPC71061753A GA500 Technical Manual
Table 12.66 KEB Ride-Thru Function Operation Method
Operation
12.9 L: Protection Functions
Configuration Precautions
• Set C1-09 correctly to prevent Uv1 [DC Bus Undervoltage] and ov
[Overvoltage].
• If the drive detects Uv1 during the KEB operation, decrease the
value set in C1-09.
• If the drive detects ov during the KEB operation, increase the value
set in C1-09.
• If the drive detects Uv1 during the KEB operation, increase the
setting value of L3-20 [DC Bus Voltage Adjustment Gain] and L3-
21 [OVSuppression Accel/Decel P Gain].
• If the drive detects ov during the KEB operation, decrease the
setting values of L3-20 and L3-21.
Use the dynamic braking option with System KEB Ride-Thru 1.
If you cannot use the dynamic braking option, use System KEB Ride-
Thru 2.
12
671