12.8 H: Terminal Function Selection
ON : Normal operation
OFF : Deceleration during momentary power loss
When you enable KEB Ride-Thru 1, set L2-29 [KEB Method Selection]. The drive operates with the selected
KEB method.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 65, 66] and KEB Ride-Thru 2 [H1-xx = 7A, 7B] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
• Refer to "KEB Ride-Thru function" for more information.
66: KEB Ride-Thru 1 Activate (N.O.)
Setting Value
Function
66
KEB Ride-Thru 1 Activate
(N.O.)
ON : Deceleration during momentary power loss
OFF : Normal operation
When you enable KEB Ride-Thru 1, set L2-29 [KEB Method Selection]. The drive operates with the selected
KEB method.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 65, 66] and KEB Ride-Thru 2 [H1-xx = 7A, 7B] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
• Refer to "KEB Ride-Thru function" for more information.
67: Communications Test Mode
Setting Value
Function
67
Communications Test Mode
The Self-Diagnostics function connects the transmission terminal of the control terminal block to the reception
terminal. The function transmits the data that the drive sent to make sure that the drive can communicate correctly.
Note:
Refer to MEMOBUS/Modbus communications "Self-Diagnostics" for the self-diagnostics procedure.
68: High Slip Braking (HSB) Activate
Setting Value
Function
68
High Slip Braking
Note:
• When you restart the drive after you use high-slip braking, make sure that the drive fully stops the motor then clear the high-slip
braking input.
• Refer to "n3: High Slip/Overex Braking" for more information.
6A: Drive Enable
Setting Value
Function
6A
Drive Enable
If you input the Run command before you turn ON the Drive Enable terminal, you must input the Run command
again to operate the drive. When the terminal set for Drive Enable is turned OFF when the drive is operating, the
drive will use the stopping method set in b1-03 [Stopping Method Selection] to stop the motor.
ON : Run command is accepted.
OFF : Run command is disabled. When the drive is running, it stops according to b1-03 setting.
75: Up 2 Command
Setting Value
Function
75
Up 2 Command
616
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Set the function for the drive to self-test RS-485 serial communications operation.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the command to use high-slip braking to stop the motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands when the terminal is OFF.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to increase the frequency reference bias value to accelerate the motor when the terminal is activated. Set this
function and H1-xx = 76 [Down 2 Command] together.
Description
Description
Description
Description
Description