Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
F: Not Used
Setting Value
Function
F
Not Used
10: Alarm
Setting Value
Function
10
Alarm
11: Fault Reset Command Active
Setting Value
Function
11
Fault Reset Command
Active
12: Timer Output
Setting Value
Function
12
Timer Output
Note:
Refer to "b4: Timer Function" for more information.
13: Speed Agree 2
Setting Value
Function
13
Speed Agree 2
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
14: User-Set Speed Agree 2
Setting Value
Function
14
User-Set Speed Agree 2
Note:
The detection level set with L4-03 is a signed value. The drive will only detect in one direction.
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact output via
MEMOBUS/Modbus or the communication option. This signal does not function if signals from the PLC are not configured.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal turns on when the drive detects a minor fault.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal turns on when the drive receives the Reset command from the control circuit terminal, serial communications, or
the communication option.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Use this setting when the drive uses the timer function as an output terminal.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection
Width(+/-)].
Figure 12.82 Speed Agree 2 Time Chart
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level(+/-)] ± L4-04 [Speed
Agree Detection Width(+/-)] and in the range of the frequency reference ± L4-04.
12.8 H: Terminal Function Selection
Description
Description
Description
Description
Description
Description
12
633