3.15 Protect the Drive during Failures
Drive Model
B012
B018
Three-Phase 400 V Class
Table 3.19 Factory-Recommended Branch Circuit Protection: Three-Phase 400 V Class
Drive Model
4001
4002
4004
4005
4007
4009
4012
4018
4023
4031
4038
4044
4060
104
Maximum Applicable Motor Output
kW (HP)
ND
HD
3.0 (3)
2.2 (3)
-
4.0 (5)
Maximum Applicable Motor Output
kW (HP)
ND
HD
0.37 (1/2)
0.37 (1/2)
0.75 (1)
0.55 (3/4)
1.5 (2)
1.1 (2)
2.2 (3)
1.5 (3)
3.0 (4)
2.2 (3)
4.0 (5)
3.0 (4)
5.5 (7.5)
4.0 (5)
7.5 (10)
5.5 (10)
11.0 (15)
7.5 (10)
15.0 (20)
11.0 (15)
18.5 (25)
15.0 (20)
22.0 (30)
18.5 (25)
30.0 (40)
22.0 (30)
Semiconductor Protection Fuse Rated Current
Time Delay Fuse
Class J, T, and CC Fuse
Rated Current
A
30
-
Semiconductor Protection Fuse Rated Current
Time Delay Fuse
Class J, CC, and T Fuse
Rated Current
A
3
6
10
10
15
20
25
-
-
-
-
-
-
YASKAWA SIEPC71061753A GA500 Technical Manual
Manufacturer: EATON/Bussmann
Input Rated Current
Model
A
FWH-125B
125
FWH-150B
150
Manufacturer: EATON/Bussmann
Input Rated Current
Model
A
FWH-40B
40
FWH-40B
40
FWH-50B
50
FWH-70B
70
FWH-70B
70
FWH-90B
90
FWH-90B
90
FWH-80B
80
FWH-100B
100
FWH-125B
125
FWH-175B
175
FWH-200B
200
FWH-200B
200