T2: PM Motor Auto-Tuning

No.
Name
(Hex.)
T2-01
PM Auto-Tuning
Selection
(0750)
T2-02
PM Motor Code
Selection
(0751)
T2-03
PM Motor Type
(0752)
T2-04
PM Motor Rated Power
(0730)
T2-05
PM Motor Rated Voltage
(0732)
T2-06
PM Motor Rated Current
(0733)
T2-07
PM Motor Base
Frequency
(0753)
T2-08
Number of PM Motor
Poles
(0734)
T2-09
PM Motor Base Speed
(0731)
T2-10
PM Motor Stator
Resistance
(0754)
T2-11
PM Motor d-Axis
Inductance
(0735)
T2-12
PM Motor q-Axis
Inductance
(0736)
T2-13
Back-EMF Units
Selection
(0755)
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to enable Test Mode after Stationary Auto-Tuning. When you can
operate the motor with a light load attached after Stationary Auto-Tuning is complete,
enable this parameter.
Note:
You must first set T1-10 = 0 [Motor Rated Slip Frequency = 0 Hz] to enable this
parameter.
0 : No
1 : Yes
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the no-load voltage of the motor. When the no-load voltage at rated speed is
available, for example on the motor test report, set the voltage in this parameter. If the
no-load voltage is not available, do not change this parameter.
Note:
To get the same qualities as a Yaskawa 1000-series drive or previous series drive,
set this parameter = T1-03 [Motor Rated Voltage].
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the type of Auto-Tuning for PM motors.
0 : Manual Entry w/ Motor Data Sheet
1 : Stationary (Ld, Lq, R)
2 : Stationary (R Only)
4 : PM Motor Code Selection
5 : High Frequency Injection
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
If the drive is operating an SMRD, SMRA, or SSR1 series Yaskawa PM motor, enter
the PM motor code in to align with the rotation speed and motor output.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the type of PM motor the drive will operate.
0 : IPM motor
1 : SPM motor
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Uses the units set in o1-58 [Motor Power Unit Selection] to set the PM motor rated
output power.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the rated voltage (V) of the motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the rated current (A) of the motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the base frequency (Hz) of the motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the number of motor poles.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the motor base speed (min
-1
(r/min)).
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the stator resistance for each motor phase.
Note:
This parameter does not set line-to-line resistance.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the d-axis inductance of the motor on a per phase basis.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the q-Axis inductance of the motor on a per phase basis.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the units that the drive uses to set the induced voltage constant.
0 : mV/(rev/min)
1 : mV/(rad/sec)
11.16 T: Motor Tuning
Default
Ref.
(Range)
0
752
(0, 1)
T1-03 × 0.9
752
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
Default
Ref.
(Range)
0
753
(Determined by A1-02)
Determined by A1-02
753
and o2-04
(0000 - FFFF)
1
753
(0, 1)
Determined by o2-04,
753
C6-01
(0.00 - 650.00 kW)
200 V Class: 200.0 V,
754
400 V: 400.0 V
(200 V Class: 0.0 - 255.0
V, 400 V Class: 0.0 -
510.0 V)
Determined by o2-04
754
(10% to 200% of the
drive rated current)
87.5 Hz
754
(0.0 - 590.0 Hz)
6
754
(2 - 48)
1750 min
-1
(r/min)
754
(0 - 34500 min
-1
(r/min))
Determined by T2-02
754
(0.000 - 65.000 Ω)
Determined by T2-02
754
(0.00 - 600.00 mH)
Determined by T2-02
754
(0.00 - 600.00 mH)
1
754
(0, 1)