12.5 d: References
Multi-Step Speed
Related Parameters
Reference 16 (d1-16)
*1
Jog Reference (d1-17)
*1
The Jog Frequency Reference (JOG command) overrides all other frequency references.
Figure 12.49 Time Chart for Multi-step Speed Reference/JOG Reference
d1-01: Reference 1
No.
Name
(Hex.)
d1-01
Reference 1
(0280)
RUN
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change. Calculate the upper limit value with this formula:
Upper limit value = (E1-04) × (d2-01) / 100
• When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
• To set d1-01 to 1-step speed parameter in a multi-step speed operation, set b1-01 = 0 [Frequency Reference Selection 1 = Keypad].
d1-02: Reference 2
No.
Name
(Hex.)
d1-02
Reference 2
(0281)
RUN
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6 [Control Method Selection = AOLV/PM], the drive sets o1-03 = 1 [0.01% (100% = E1-04)].
• To set d1-02 to Multi-Step Speed 2, set H3-02 and 3-10 ≠ 2 [MFAI Function Select ≠ Auxiliary Frequency Reference 1].
542
Multi-Step Speed
Reference 1
Reference 2
H1-xx = 3
H1-xx = 4
ON
ON
-
-
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Multi-Step Speed
Multi-Step Speed
Reference 3
Reference 4
H1-xx = 5
H1-xx = 32
ON
-
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Jog Reference
H1-xx = 6
ON
OFF
-
ON
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)