12.8 H: Terminal Function Selection
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is
running.
3: User-Set Speed Agree 1
Setting Value
Function
3
User-Set Speed Agree 1
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection
level.
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency
reference ± L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" nor the range of frequency
reference ± L4-02.
4: Frequency Detection 1
Setting Value
Function
4
Frequency Detection 1
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection
level.
ON : The output frequency is less than the value of L4-01 or does not exceed the value of L4-01 +
L4-02.
OFF : The output frequency is higher than the value of L4-01 + L4-02.
630
Figure 12.78 Speed Agree 1 Time Chart
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
Figure 12.79 User-Defined Speed Agree 1 Time Chart
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection Level] + L4-02
[Speed Agree Detection Width]. After the terminal turns off, the terminal continues to remain off until the output frequency
reaches the level set with L4-01.
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents