12.9 L: Protection Functions
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
1110 : Enabled (oL1/oL2/oL3/—)
1111 : Enabled (oL1/oL2/oL3/oL4)
L5-08: Fault Reset Enable Select Grp2
No.
Name
(Hex.)
L5-08
Fault Reset Enable Select
Grp2
(0B2B)
0000 : Disabled
0001 : Enabled (—/–/—/GF)
0010 : Enabled (—/–/oH1/–)
0011 : Enabled (—/–/oH1/GF)
0100 : Enabled (—/ov/—/–)
0101 : Enabled (—/ov/—/GF)
0110 : Enabled (—/ov/oH1/–)
0111 : Enabled (—/ov/oH1/GF)
1000 : Enabled (Uv1/–/—/–)
1001 : Enabled (Uv1/–/—/GF)
1010 : Enabled (Uv1/–/oH1/–)
1011 : Enabled (Uv1/–/oH1/GF)
1100 : Enabled (Uv1/ov/—/–)
1101 : Enabled (Uv1/ov/—/GF)
1110 : Enabled (Uv1/ov/oH1/–)
1111 : Enabled (Uv1/ov/oH1/GF)

L6: Torque Detection

The overtorque/undertorque detection function prevents damage to machinery and loads.
Overtorque is the when there is too much load on the machine. If the motor current or output torque is at the
overtorque detection level for the overtorque detection time, the drive will output an alarm and turn off the output.
Undertorque is the when a load suddenly decreases. When the motor current or output torque is at the undertorque
detection level for the undertorque detection time, the drive will outupt an alarm and turn off the output.
You can use the undertorque detection function to detect these conditions, for example:
• Machine belt cuts
• Unusual operation of the electromagnetic contactor on the drive output side
• Clogged output side air filters in fans and blowers
694
Figure 12.123 Setting Digits and Fault Code
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From left to right,
the digits set Uv1, ov, oH1, and GF, in order.
Figure 12.124 Setting Digits and Fault Code
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
1111
(0000 - 1111)