12.11 o: Keypad-Related Settings
o2-04: Drive Model (KVA) Selection
No.
Name
(Hex.)
o2-04
Drive Model (KVA)
Selection
(0508)
NOTICE: Set o2-04 [Drive Model Selection] correctly. If you set this parameter incorrectly, it will decrease drive performance,
cause the protection function to operate incorrectly, and cause damage to the drive.
Note:
When the setting value of o2-04 changes, related parameter setting values also change. Refer to
Rating ND/HD on page 431
These tables list the relation between o2-04 setting values and drive models.
o2-04 Setting
30
31
32
33
34
35
37
60
61
62
63
64
65
66
67
68
91
o2-05: Home Mode Freq Ref Entry Mode
No.
Name
(Hex.)
o2-05
Home Mode Freq Ref Entry
Mode
(0509)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is
not necessary to push
the keypad to change the frequency reference value.
o2-06: Keypad Disconnect Detection
No.
Name
(Hex.)
o2-06
Keypad Disconnect
Detection
(050A)
738
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Drive Model code. Set this parameter after replacing the control board.
for more information.
Drive Model
B001
B002
B004
B006
B010
B012
B018
2001
2002
2004
2006
2008
2010
2012
2018
2021
2030
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that makes it necessary to push
reference value while in Drive Mode.
. The drive keeps the frequency reference for 5 seconds after you use
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive
or if you damage the cable while the keypad is the Run command source.
Description
Defaults by Drive Model and Duty
o2-04 Setting
92
93
94
95
96
97
99
6A
6B
6D
6E
6F
9A
9C
9D
9E
9F
Description
to use the keypad to change the frequency
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Setting Range)
Determined by the drive
(-)
Drive Model
2042
2056
2070
2082
4001
4002
4004
4005
4007
4009
4012
4018
4023
4031
4038
4044
4060
Default
(Setting Range)
0
(0, 1)
and
on
Default
(Range)
0
(0, 1)