No.
Name
(Hex.)
b5-38
PID User Unit Display
Scaling
(01FE)
b5-39
PID User Unit Display
Digits
(01FF)
b5-40
Frequency Reference
Monitor @PID
(017F)
b5-47
PID Trim Mode Output
Reverse Sel
(017D)
b5-53
PID Integrator Ramp
Limit
(0B8F)
RUN
b5-55
PID Feedback Monitor
Selection
(0BE1)
b5-56
PID Feedback Monitor
Gain
(0BE2)
b5-57
PID Feedback Monitor
Bias
(11DD)
b5-58 to b5-60:
PID Setpoints 2 to 4
(1182 - 1184)
RUN
b5-61
PID Trim Mode Lower
Limit Sel
(119A)
b5-62
PID Trim Mode Lower
Limit Value
(119B)
b5-63
PID Differential FB
Monitor Sel
(119C)
b5-64
PID Differential FB
Monitor Gain
(119D)
b5-65
PID Differential FB
Monitor Bias
(119F)
b5-66
PID Feedback Monitor
Level
(11DE)
b5-67
PID Differential FB
Monitor Lvl
(11DF)
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the value that the drive sets or shows as the PID setpoint when at the maximum
output frequency.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the number of digits to set and show the PID setpoint.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the contents for monitor U1-01 [Frequency Reference] in PID control.
0 : U1-01 Includes PID Output
1 : U1-01 Excludes PID Output
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets reverse motor rotation when the PID control output is negative.
0 : Lower Limit is Zero
1 : Negative Output Accepted
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the responsiveness of PID control when the PID feedback changes quickly.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the monitor (Ux-xx) used as the PID Feedback. Set the x-xx part of the Ux-xx
[Monitor].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for the monitor set in b5-55 [PID Feedback Monitor Selection].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the bias for the monitor specified in b5-55 [PID Feedback Monitor Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function Selection = PID
Setpoint Selection 1/2]. This value is a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that adjusts the PID output in relation to the frequency reference.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the PID Trim Mode Lower Limit Value as a percentage of the maximum output
frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the
maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Selects the monitor (Ux-xx) used as the PID Differential Feedback. Set the x-xx part of
the Ux-xx [Monitor].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bias for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the signal level for the monitor specified in b5-55 [PID Feedback Monitor
Selection].
0 : Absolute
1 : Bi-directional (+/-)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the signal level for the monitor specified in b5-63 [PID Differential FB Monitor
Sel].
0 : Absolute
1 : Bi-directional (+/-)
11.5 b: Application
Default
Ref.
(Range)
Determined by b5-20
510
(1 - 60000)
Determined by b5-20
510
(0 - 3)
0
510
(0, 1)
1
511
(0, 1)
0.0 Hz
511
(0.0 - 10.0 Hz)
000
511
(000 - 999)
1.00
512
(0.00 - 10.00)
0.00
512
(-10.00 - +10.00)
0.00%
512
(0.00 - 100.00%)
0
512
(0, 1)
0.00%
512
(0.00 - 100.00%)
000
513
(000 - 999)
1.00
513
(0.00 - 10.00)
0.00
513
(-10.00 - +10.00)
0
513
(0, 1)
0
513
(0, 1)
345
11

Advertisement