YASKAWA CIPR-GA50C series Technical Manual page 693

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

L5-01: Number of Auto-Restart Attempts
No.
Name
(Hex.)
L5-01
Number of Auto-Restart
Attempts
(049E)
The drive resets the number of Auto Restart attempts to 0 in these conditions:
• The drive operates correctly for 10 minutes after a fault restart.
• When you manually clear a fault after the drive triggers protective functions.
• When you re-energize the drive.
L5-02: Fault Contact at Restart Select
No.
Name
(Hex.)
L5-02
Fault Contact at Restart
Select
(049F)
0 : Active Only when Not Restarting
1 : Always Active
L5-04: Interval Method Restart Time
No.
Name
(Hex.)
L5-04
Interval Method Restart
Time
(046C)
L5-05: Auto-Restart Method
No.
Name
(Hex.)
L5-05
Auto-Restart Method
(0467)
0 : Continuous/Immediate Attempts
Counts the number of successful fault resets through Auto Restart.
When this value > L5-01, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
1 : Interval/Attempt after L5-04 sec
Counts the number of all fault resets (successful and unsuccessful) through Auto Restart. The drive repeats the
Auto Restart process in the intervals set in L5-04 [Interval Method Restart Time].
When this value > L5-01, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
L5-07: Fault Reset Enable Select Grp1
No.
Name
(Hex.)
L5-07
Fault Reset Enable Select
Grp1
(0B2A)
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the number of times that the drive will try to restart.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = E] while the
drive is automatically restarting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time interval between each Auto Restart attempt. This function is enabled when L5-05 =
1 [Auto Restart Operation Selection = Use L5-04 Time].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the count method for the Auto Restart operation.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the digits set
oL1, oL2, oL3, and oL4, in order.
12.9 L: Protection Functions
Description
Description
Description
Description
Description
Default
(Range)
0
(0 - 10 times)
Default
(Range)
0
(0, 1)
Default
(Range)
10.0 s
(0.5 - 600.0 s)
Default
(Range)
0
(0, 1)
Default
(Range)
1111
(0000 - 1111)
12
693

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents