Note:
Refer to "PID Feedback Loss Detection" for more information.
3F: PID Feedback High
Setting Value
Function
3F
PID Feedback High
The drive detects FbH [Excessive PID Feedback] when the PID feedback value > b5-36 [PID High Feedback
Detection Lvl] for longer than the time set in b5-37 [PID High Feedback Detection Time].
Note:
Refer to "PID Feedback Loss Detection" for more information.
4A: During KEB Ride-Thru
Setting Value
Function
4A
During KEB Ride-Thru
Note:
Refer to "KEB Ride-Thru function" for more information.
4B: During Short Circuit Braking
Setting Value
Function
4B
During Short Circuit
Braking
Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], this function is available when you use a PM motor.
• Refer to "b2: DC Injection Braking and Short Circuit Braking" for more information.
4C: During Fast Stop
Setting Value
Function
4C
During Fast Stop
4D: oH Pre-Alarm Reduction Limit
Setting Value
Function
4D
oH Pre-Alarm Time Limit
Note:
Refer to "L8-03: Overheat Pre-Alarm Selection" for more information.
4E: Braking Transistor Fault (rr)
Setting Value
Function
4E
Braking Transistor Fault
(rr)
4F: Braking Resistor Overheat (rH)
Setting Value
Function
4F
Braking Resistor Overheat
(rH)
The braking resistor overheats when the deceleration time is short and there is too much motor regeneration
energy.
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects FbH [Excessive PID Feedback].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The activates during KEB Ride-Thru.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates during Short Circuit Braking.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the fast stop is in operation.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and oH [Heatsink
Overheat] does not clear after the drive decreases the frequency for 10 cycles.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the internal braking transistor overheats and the drive detects an rr [Dynamic Braking Transistor
Fault] fault.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the braking resistor overheats and the drive detects an rH [Braking Resistor Overheat] fault.
12.8 H: Terminal Function Selection
Description
Description
Description
Description
Description
Description
Description
12
639