12.8 H: Terminal Function Selection
H2-20: Comparator 1 Monitor Selection
No.
Name
(Hex.)
H2-20
Comparator 1 Monitor
Selection
(1540)
Note:
• For information on the comparator function, refer to
• The configurable monitor changes when the control method changes.
H2-21: Comparator 1 Lower Limit
No.
Name
(Hex.)
H2-21
Comparator 1 Lower Limit
(1541)
Note:
For information on the comparator function, refer to
H2-22: Comparator 1 Upper Limit
No.
Name
(Hex.)
H2-22
Comparator 1 Upper Limit
(1542)
Note:
For information on the comparator function, refer to
H2-23: Comparator 1 Hysteresis
No.
Name
(Hex.)
H2-23
Comparator 1 Hysteresis
(1543)
Note:
For information on the comparator function, refer to
H2-24: Comparator 1 On-Delay Time
No.
Name
(Hex.)
H2-24
Comparator 1 On-Delay
Time
(1544)
Note:
For information on the comparator function, refer to
H2-25: Comparator 1 Off-Delay Time
No.
Name
(Hex.)
H2-25
Comparator 1 Off-Delay
Time
(1545)
Note:
For information on the comparator function, refer to
624
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For example,
set H2-20 = 102 to monitor U1-02 [Output Frequency].
66: Comparator1 on page 640
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the lower limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
66: Comparator1 on page 640
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the upper limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
66: Comparator1 on page 640
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection].
66: Comparator1 on page 640
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the on-delay time for comparator 1.
66: Comparator1 on page 640
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the off-delay time for comparator 1.
66: Comparator1 on page 640
Description
and
67: Comparator2 on page
Description
and
67: Comparator2 on page
Description
and
67: Comparator2 on page
Description
and
67: Comparator2 on page
Description
and
67: Comparator2 on page
Description
and
67: Comparator2 on page
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
102
(000 - 999)
640.
Default
(Range)
0.0%
(0.0 - 300.0%)
640.
Default
(Range)
0.0%
(0.0 - 300.0%)
640.
Default
(Range)
0.0%
(0.0 - 10.0%)
640.
Default
(Range)
0.0 s
(0.0 - 600.0 s)
640.
Default
(Range)
0.0 s
(0.0 - 600.0 s)
640.