Alarm Outputs for Maintenance Monitors
You can use H2-xx [MFDO Function Selection] to send a message that tells you when a specified component is
near the end of its performance life estimate. Set the applicable value to H2-xx as shown in
component.
When the specified component is near the end of its performance life estimate, the MFDO terminals set for H2-xx
= 2F [Maintenance Notification] will activate, and the keypad will show an alarm that identifies the component to
replace.
Display
Alarm Name
Cooling Fan
LT-1
Maintenance Time
Capacitor
LT-2
Maintenance Time
SoftChargeBypassRe
LT-3
lay MainteTime
IGBT Maintenance
LT-4
Time (50%)
IGBT Maintenance
TrPC
Time (90%)
Related Parameters
Replace the component, then set o4-03, o4-05, o4-07, and o4-09 [Maintenance Setting] = 0 to reset the
Maintenance Monitor. If these parameters are not reset after the corresponding parts have been replaced, the
Maintenance Monitor function will continue to count down the performance life from the value that was reached
with the old part. If the Maintenance Monitor is not reset, the drive will not have the correct value of the
performance life for the new component.
Note:
The maintenance period changes for different operating environments.
No.
o4-03
Fan Operation Time Setting
o4-05
Capacitor Maintenance Setting
o4-07
Softcharge Relay Maintenance Set
o4-09
IGBT Maintenance Setting
YASKAWA SIEPC71061753A GA500 Technical Manual
Table 8.9 Maintenance Period Alarms
Cause
The cooling fan is at 90% of its expected
performance life.
The capacitors for the main circuit and control
circuit are at 90% of expected performance life.
The soft charge bypass relay is at 90% of its
performance life estimate.
The IGBT is at 50% of its expected performance
life.
The IGBT is at 90% of its expected performance
life.
Table 8.10 Maintenance Setting Parameters
Name
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units.
Note:
When o4-03 = 30 has been set, the drive will count the operation time for the cooling fan from 300 hours
and U4-03 [Cooling Fan Ope Time] will show 300 h.
Sets the value from which to start the count for the main circuit capacitor maintenance period as a percentage.
Sets as a percentage the value from which to start the count for the soft charge bypass relay maintenance
time.
Sets the value from which to start the count for the IGBT maintenance period as a percentage.
Possible Solutions
Replace the cooling fan, then set o4-03 = 0 [Fan Operation
Time Setting = 0 h] to reset the cooling fan operation time.
Replace the board or the drive.
Contact Yaskawa or your nearest sales representative to
replace the board.
Replace the board or the drive.
Contact Yaskawa or your nearest sales representative to
replace the board.
Check the load, carrier frequency, and output frequency.
Replace the IGBT or the drive.
Function
8.3 Maintenance
Table 8.9
for your
Digital Outputs
(Setting Value in
H2-xx)
2F
10
295
8