Setting Value
Function
3C
LOCAL Control
Selected
3D
During Speed Search
3E
PID Feedback Low
3F
PID Feedback High
4A
During KEB Ride-Thru
4B
During Short Circuit
Braking
4C
During Fast Stop
4D
oH Pre-Alarm Time
Limit
4E
Braking Transistor Fault
(rr)
4F
Braking Resistor
Overheat (rH)
61
Pole Position Detection
Complete
62
Modbus Reg 1 Status
Satisfied
63
Modbus Reg 2 Status
Satisfied
66
Comparator1
67
Comparator2
69
External Power 24V
Supply
6A
Data Logger Error
90 - 92
DWEZ Digital Output 1
to 3
100 - 192
Inverse output of 0 to 92
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
OFF : REMOTE
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive is doing speed search.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects FbL [PID Feedback Loss].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects FbH [Excessive PID Feedback].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The activates during KEB Ride-Thru.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates during Short Circuit Braking.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available when you use a PM motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the fast stop is in operation.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and
oH [Heatsink Overheat] does not clear after the drive decreases the frequency for 10 cycles.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the internal braking transistor overheats and the drive detects an rr [Dynamic Braking
Transistor Fault] fault.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the braking resistor overheats and the drive detects an rH [Braking Resistor Overheat]
fault.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position
of the PM motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register
address set with H2-07 [Modbus Register 1 Address Select] activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register
address set with H2-09 [Modbus Register 2 Address Select] activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the
values of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24
[Comparator 1 On-Delay Time].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of
the values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-
30 [Comparator 2 On-Delay Time].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects LoG [Com Error / Abnormal SD card].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which
function to inversely output.
11.10 H: Terminal Functions