Setting Value
Function
3C
LOCAL Control
Selected
3D
During Speed Search
3E
PID Feedback Low
3F
PID Feedback High
4A
During KEB Ride-Thru
4B
During Short Circuit
Braking
4C
During Fast Stop
4D
oH Pre-Alarm Time
Limit
4E
Braking Transistor Fault
(rr)
4F
Braking Resistor
Overheat (rH)
61
Pole Position Detection
Complete
62
Modbus Reg 1 Status
Satisfied
63
Modbus Reg 2 Status
Satisfied
66
Comparator1
67
Comparator2
69
External Power 24V
Supply
6A
Data Logger Error
90 - 92
DWEZ Digital Output 1
to 3
100 - 192
Inverse output of 0 to 92
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
OFF : REMOTE
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive is doing speed search.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects FbL [PID Feedback Loss].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects FbH [Excessive PID Feedback].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The activates during KEB Ride-Thru.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates during Short Circuit Braking.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available when you use a PM motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the fast stop is in operation.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and
oH [Heatsink Overheat] does not clear after the drive decreases the frequency for 10 cycles.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the internal braking transistor overheats and the drive detects an rr [Dynamic Braking
Transistor Fault] fault.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the braking resistor overheats and the drive detects an rH [Braking Resistor Overheat]
fault.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when drive receives a Run command and the drive detects the motor magnetic pole position
of the PM motor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register
address set with H2-07 [Modbus Register 1 Address Select] activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register
address set with H2-09 [Modbus Register 2 Address Select] activates.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the
values of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24
[Comparator 1 On-Delay Time].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of
the values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-
30 [Comparator 2 On-Delay Time].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects LoG [Com Error / Abnormal SD card].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which
function to inversely output.
11.10 H: Terminal Functions
Description
Ref.
638
638
638
639
639
639
639
639
639
639
640
640
640
640
640
641
641
641
641
11
379

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents