5.3 UL Standards
Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4044
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4060
-, +1, +2
B1, B2
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
Factory-Recommended Branch Circuit Protection for UL Listing
Use branch circuit protection to protect against short circuits and to maintain compliance with UL61800-5-1.
Yaskawa recommends connecting semiconductor protection fuses on the input side for branch circuit protection.
Refer to
Three-Phase 400 V Class on page
Class on page 189
for more information.
WARNING! Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not immediately energize the drive
or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators
are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of
the problem, contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you
operate the drive or peripheral devices, it can cause serious injury or death.
• 200 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
31,000 RMS and not more than 240 Vac when there is a short circuit in the power supply.
• 400 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than
31,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric Code (NEC), the Canadian Electric Code, Part I
(CEC), and local codes.
188
Recommended
Applicable Gauge
Gauge
AWG, kcmil
AWG, kcmil
4
10 - 2
6
12 - 4
2
8 - 2
8
12 - 6
6
10 - 6
2
8 - 2
4
10 - 2
2
6 - 2
8
12 - 6
6
10 - 6
189,
Single-Phase 200 V Class on page
Wire
Terminal Screw
Stripping
*1
Length
Size
Shape
mm
18
M5
18
M5
18
M5
10
M4
-
M6
18
M5
18
M5
18
M5
10
M4
-
M6
189, and
YASKAWA SIEPC71061753A GA500 Technical Manual
Tightening Torque
N∙m (in∙lb)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
• AWG 8 ≤
4.1 - 4.5
(36 - 40)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
• AWG 8 ≤
4.1 - 4.5
(36 - 40)
4.1 - 4.5
(36 - 40)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
4.1 - 4.5
(36 - 40)
• ≤ AWG 10
2.3 - 2.5
(19.8 - 22)
• AWG 8 ≤
4.1 - 4.5
(36 - 40)
4.1 - 4.5
(36 - 40)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
2
(copper wire).