11.17 U: Monitors

U1: Operation Status Monitors

No.
Name
(Hex.)
U1-01
Frequency reference
(0040)
U1-02
Output Frequency
(0041)
U1-03
Output Current
(0042)
U1-04
Control method selection
(0043)
U1-05
Motor Speed
(0044)
U1-06
Output Voltage Ref
(0045)
U1-07
DC Bus Voltage
(0046)
U1-08
Output Power
(0047)
U1-09
Torque Reference
(0048)
U1-10
Input Terminal Status
(0049)
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the actual frequency reference value. Parameter o1-03 [Keypad Display Unit Selection]
sets the display units.
Unit: 0.01 Hz
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the actual output frequency. Parameter o1-03 [Keypad Display Unit Selection] sets the
display units.
Unit: 0.01 Hz
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the actual output current.
The keypad shows the value of U1-03 in amperes (A). When looking at the monitor through
MEMOBUS/Modbus communications, the current is "8192 = drive rated current (A)". Calculate
the current from the monitor value that is in at MEMOBUS/Modbus communications using
"Numerals being displayed / 8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
• 0.01 A units: 2001 to 2042, B001 to B018, 4001 to 4023
• 0.1A units: 2056 to 2082, 4031 to 4060
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the drive control method.
0 : V/f Control
2 : Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
8 : EZ Vector Control
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the actual detected motor speed. Parameter o1-03 [Keypad Display Unit Selection] sets the
display units.
Unit: 0.01 Hz
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the output voltage reference.
Unit: 0.1 V
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the DC bus voltage.
Unit: 1 V
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the internally-calculated output power.
Changing the setting of A1-02 [Control Method Selection] also changes the signal level of the
analog output.
• A1-02 = 0: Drive capacity (kW)
• A1-02 = 2: Motor Rated Power [E2-11] (kW)
• A1-02 = 5, 6: PM Motor Rated Power [E5-02] (kW)
• A1-02 = 8: Motor Rated Power [E9-07] (kW)
Unit: When the drive model changes, the display units for this parameter also change.
• 0.01 A units: 2001 to 2042, B001 to B018, 4001 to 4023
• 0.1A units: 2056 to 2082, 4031 to 4060
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the internal torque reference value.
Unit: 0.1%
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the status of the MFDO terminal where
For example, U1-10 shows
bit0 : Terminal S1 (MFDI 1)
bit1 : Terminal S2 (MFDI 2)
bit2 : Terminal S3 (MFDI 3)
bit3 : Terminal S4 (MFDI 4)
bit4 : Terminal S5 (MFDI 5)
bit5 : Terminal S6 (MFDI 6)
bit6 : Terminal S7 (MFDI 7)
bit7 : Not used (normal value of [ ]).
Description
= ON and
= OFF.
when terminals S1 and S3 are ON.

11.17 U: Monitors

MFAO Signal Level
10 V = Maximum
frequency (-10 V to +10 V)
10 V = Maximum
frequency (-10 V to +10 V)
10 V = Drive rated current
No signal output available
10 V = Maximum
frequency (-10 V to +10 V)
200 V class: 10 V = 200
Vrms
400 V class: 10 V = 400
Vrms
200 V class: 10 V = 400 V
400 V class: 10 V = 800 V
10 V: Drive capacity (motor
rated power) kW
(-10 V to +10 V)
10 V = Motor rated torque
(-10 V to +10 V)
No signal output available
11
413