The Motor Will Not Restart after a Loss of Power

Causes
The drive did not receive a Run command after applying power.
For applications that use 3-wire sequence, the momentary power loss
continued for a long time, and the relay that keeps the Run command has
been switched off.
YASKAWA SIEPC71061753A GA500 Technical Manual
7.10 Troubleshooting Without Fault Display
Possible Solutions
• Examine the sequence and wiring that enters the Run command.
• Set up a relay to make sure that the Run command stays enabled during a loss of power.
Examine the wiring and circuitry for the relay that keeps the Run command enabled during the
momentary power loss ride-thru time.