12.5 d: References
Remove the Saved Frequency Reference Value
The procedure to remove the saved frequency reference value is different for different functions. Use these
methods to remove the value:
• Release the input programmed for Accel/Decel Ramp Hold [H1-xx = A].
• Set an Up or Down command while no Run command is active.
• Use the Up/Down 2 Command to set d4-06 = 0.0 or set d4-06 = 0.0 during stop.
d4-03: Up/Down 2 Bias Step Frequency
No.
Name
(Hex.)
d4-03
Up/Down 2 Bias Step
Frequency
(02AA)
RUN
The operation is different for different setting values:
• Setting d4-03 = 0.00 Hz
When the Up/Down 2 Command [H1-xx = 75, 76] is active, the drive uses the accel/decel times set in d4-04
[Up/Down 2 Ramp Selection] to increase or decrease the bias value.
• Setting d4-03 ≠ 0.00 Hz
When the Up/Down 2 Command [H1-xx = 75, 76] is active, the drive increases or decreases the bias in steps for
the value set in d4-03. The drive uses the acceleration and deceleration times set in d4-04.
d4-04: Up/Down 2 Ramp Selection
No.
Name
(Hex.)
d4-04
Up/Down 2 Ramp Selection
(02AB)
RUN
0 : Use Selected Accel/Decel Time
Use the active acceleration and deceleration times to increase or decrease the bias.
1 : Use Accel/Decel Time 4
Use C1-07 [Acceleration Time 4] and C1-08 [Deceleration Time 4] to increase or decrease the bias.
550
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the bias that the Up/Down 2 function adds to or subtracts from the frequency reference.
Figure 12.55 Up/Down 2 Bias when d4-03 = 0.00 Hz
Figure 12.56 Up/Down 2 Bias when d4-03 ≠ 0.00 Hz
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the acceleration and deceleration times for the Up/Down 2 function to apply the bias to the
frequency reference.
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
0.00 Hz
(0.00 - 99.99 Hz)
Default
(Range)
0
(0, 1)