C3: Slip Compensation

No.
Name
(Hex.)
C3-01
Slip Compensation Gain
(020F)
RUN
C3-02
Slip Compensation
Delay Time
(0210)
RUN
C3-03
Slip Compensation Limit
(0211)
C3-04
Slip Compensation at
Regen
(0212)
C3-05
Output Voltage Limit
Selection
(0213)
C3-16
Vout Modulation Limit
Start Lvl
(0261)
Expert
C3-17
Vout Modulation Limit
Max Level
(0262)
Expert
C3-18
Output Voltage Limit
Level
(0263)
Expert
C3-21
Motor 2 Slip
Compensation Gain
(033E)
RUN
C3-22
Motor 2 Slip Comp
Delay Time
(0241)
RUN
C3-23
Motor 2 Slip
Compensation Limit
(0242)
C3-24
Motor 2 Slip Comp
during Regen
(0243)
C3-29
Slip Compensation Gain
@ Low Spd
(1B5D)
Expert
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain for the slip compensation function. Usually it is not necessary to change
this setting.
Note:
Correctly set these parameters before changing the slip compensation gain:
• E2-01 [Motor Rated Current (FLA)]
• E2-02 [Motor Rated Slip]
• E2-03 [Motor No-Load Current]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the slip compensation delay time when speed is unstable or when the slip
compensation response is too slow. Usually it is not necessary to change this setting.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the upper limit for the slip compensation function as a percentage of the motor
rated slip.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the slip compensation function during regenerative operation.
0 : Disabled
1 : Enabled Above 6Hz
2 : Enabled Above C3-15
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the automatic reduction of motor magnetic flux when the output voltage is
saturated.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the modulation factor that starts the output voltage limit operation when C3-05 = 1
[Output Voltage Limit Selection = Enabled].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the modulation factor used with C3-18 [Output Voltage Limit Level] for the output
voltage limit operation when C3-05 = 1 [Output Voltage Limit Selection = Enabled].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the maximum drop width of the voltage reference when C3-05 = 1 [Output Voltage
Limit Selection = Enabled].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for the motor 2 slip compensation function. Usually it is not necessary to
change this setting.
Note:
Correctly set these parameters before changing the slip compensation gain:
• E4-01 [Motor 2 Rated Current]
• E4-02 [Motor 2 Rated Slip]
• E4-03 [Motor 2 Rated No-Load Current]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the slip compensation delay time for motor 2 when speed is unstable or when the
slip compensation response is too slow. Usually it is not necessary to change this
setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the upper limit for the slip compensation function as a percentage of the motor 2
rated slip.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the slip compensation during regenerative operation function for motor 2.
0 : Disabled
1 : Enabled Above 6Hz
2 : Enabled Above C3-15
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for the slip compensation function in the low speed range. Usually it is not
necessary to change this setting.
11.6 C: Tuning
Default
Ref.
(Range)
Determined by A1-02
526
(0.0 - 2.5)
Determined by A1-02
526
(0 - 10000 ms)
200%
527
(0 - 250%)
0
527
(0 - 2)
0
527
(0, 1)
90.0%
528
(70.0 - 90.0%)
100.0%
528
(85.0 - 100.0%)
90.0%
528
(50.0 - 100.0%)
Determined by E3-01
528
(0.0 - 2.5)
Determined by E3-01
528
(0 - 10000 ms)
200%
529
(0 - 250%)
0
529
(0 - 2)
0.0
529
(0.0 - 2.5)
349
11