Setting Value
Function
2
Auxiliary Frequency
Reference 1
3
Auxiliary Frequency
Reference 2
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking
Current
7
Torque Detection Level
8
Stall Prevent Level
during Run
9
Output Frequency Lower
Limit
B
PID Feedback
C
PID Setpoint
D
Frequency Bias
E
Motor Temperature
(PTC Input)
F
Not Used
10
Forward Torque Limit
11
Reverse Torque Limit
12
Regenerative Torque
Limit
13
Torque Reference /
Torque Limit
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets Reference 2 through multi-step speed reference to enable the command reference (Auxiliary Frequency
Reference 1) from the analog input terminal set here. This value is a percentage where the Maximum Output
Frequency setting is a setting value of 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets Reference 3 through multi-step speed reference to enable the command reference (Auxiliary Frequency
Reference 2) from the analog input terminal set here. This value is a percentage where the Maximum Output
Frequency setting is a setting value of 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Set this parameter to input a bias signal to amplify the output voltage.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enters a signal to adjust the gain used for C1-01 to C1-08 [Acceleration/Deceleration Times 1 to 4] and C1-09
[Fast Stop Time] when the full scale analog signal (10 V or 20 mA) is 100%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is
100%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enters a signal to adjust the overtorque/undertorque detection level.
Note:
Use this function with L6-01 [Torque Detection Selection 1]. This parameter functions as an alternative to L6-
02 [Torque Detection Level 1].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters a signal to adjust the output frequency lower limit level as a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enter the PID feedback value as a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enters the PID setpoint as a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters the bias value added to the frequency reference as a percentage of the maximum output frequency.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor as a
percentage of the current value when the 10 V analog signal is input.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters the forward torque limit if the motor rated torque is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters the load torque limit if the motor rated torque is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters the regenerative torque limit if the motor rated torque is 100%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enters the torque reference if the motor rated torque is 100%. This setting is the torque limit for speed control.
11.10 H: Terminal Functions
Description
Ref.
647
647
647
647
648
648
648
649
649
649
649
649
649
650
651
651
11
651
381