YASKAWA CIPR-GA50C series Technical Manual page 259

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

Code
Name
UL4
Undertorque Detection 2
Note:
• The drive detects this error if the drive output current is less than the level set in L6-05 for longer than L6-06.
• Do a Fault Reset to clear the fault.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-04 [Torque Detection Selection 2].
Code
Name
UL5
Mechanical Weakening Detection 2
Note:
• Do a Fault Reset to clear the fault.
• If the drive detects this error, it will operate the motor as specified by the Stopping Method set in L6-08.
Code
Name
Uv1
DC Bus Undervoltage
Note:
• The drive detects this error if the DC bus voltage decreases below the level set in L2-05 [Undervoltage Detection Lvl (Uv1)] while the drive is running.
• The Uv1 detection level is approximately 190 V for a 200 V class drives. The detection level is approximately 380 V for 400 V class drives. The detection level is
approximately 350 V when E1-01 [Input AC Supply Voltage] < 400.
• Do a Fault Reset to clear the fault.
• Fault trace is not available for this fault.
• L5-08 [Fault Reset Enable Select Grp2] disables the Auto Restart function.
Code
Name
Uv2
Control Power Undervoltage
Note:
• The drive detects this error if the control power supply voltage decreases.
• Do a Fault Reset to clear the fault.
• Fault trace is not available for this fault.
Code
Name
Uv3
Soft Charge Answerback Fault
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for these faults.
YASKAWA SIEPC71061753A GA500 Technical Manual
Causes
A fault occurred on the machine.
Example: There is a broken pulley belt.
The parameters are incorrect for the load.
Causes
The drive detected undertorque as specified by the
conditions for mechanical weakening detection set
in L6-08 [Mechanical Fatigue Detect Select].
Causes
There is a phase loss in the drive input power.
There is loose wiring in the drive input power
terminals.
The drive input power voltage is changing too
much.
There was a loss of power.
The main circuit capacitors have become
unserviceable.
The relay or contactor on the soft-charge bypass
relay is damaged.
Causes
The value set in L2-02 [Power Loss Ride Through
Time] increased and the momentary power loss
recovery unit is not connected to the drive.
There was a problem with the drive hardware.
Causes
The relay or contactor on the soft-charge bypass
relay is damaged.
Possible Solutions
Examine the machine and remove the cause of the fault.
Adjust L6-05 [Torque Detection Level 2] and L6-06 [Torque
Detection Time 2] settings.
Possible Solutions
Examine the machine for deterioration.
Possible Solutions
Correct errors with the wiring for main circuit drive input power.
Tighten the terminal screws to the correct tightening torque.
• Examine the input power for problems.
• Make the drive input power stable.
• If the input power supply is good, examine the magnetic
contactor on the main circuit side for problems.
Use a better power supply.
Examine the capacitor maintenance time in monitor U4-05
[CapacitorMaintenance]. If U4-05 is more than 90%, replace the
control board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales
representative.
U4-06 [PreChargeRelayMainte] shows the performance life of
the soft-charge bypass relay. If U4-06 is more than 90%, replace
the board or the drive. For information about replacing the board,
contact Yaskawa or your nearest sales representative.
Possible Solutions
Connect the momentary power loss recovery unit to the drive.
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact
Yaskawa or your nearest sales representative.
Possible Solutions
• Re-energize the drive.
• If the fault stays, replace the control board or the drive.
• Check monitor U4-06 [PreChargeRelayMainte] shows the
performance life of the soft-charge bypass relay. If U4-06 is
more than 90%, replace the board or the drive. For information
about replacing the control board, contact Yaskawa or your
nearest sales representative.
7.4 Faults
7
259