12.8 H: Terminal Function Selection
H5-25: Function 5A Register 1 Selection
No.
Name
(Hex.)
H5-25
Function 5A Register 1
Selection
(1589)
RUN
H5-26: Function 5A Register 2 Selection
No.
Name
(Hex.)
H5-26
Function 5A Register 2
Selection
(158A)
RUN
H5-27: Function 5A Register 3 Selection
No.
Name
(Hex.)
H5-27
Function 5A Register 3
Selection
(158B)
RUN
H5-28: Function 5A Register 4 Selection
No.
Name
(Hex.)
H5-28
Function 5A Register 4
Selection
(158C)
RUN

H6: Pulse Train Input/Output

H6 parameters set the drive pulse train input and pulse train monitor. These parameters select input and monitor
parameters and adjust the pulse train frequency.
A pulse train signal with a maximum single pulse of 32 kHz can be input to the drive input terminal RP. You can
use the pulse train signal as the frequency reference, PID feedback value, PID setpoint value, and speed feedback
for V/f Control mode.
A pulse train signal with a maximum frequency of 32 kHz can be output from the drive output terminal MP as the
monitor value. Sinking mode and sourcing mode are supported.
H6-01: Terminal RP Pulse Train Function
No.
Name
(Hex.)
H6-01
Terminal RP Pulse Train
Function
(042C)
0 : Frequency Reference
When b1-01 [Frequency Reference Selection 1] or b1-15 [Frequency Reference Selection 2] = 4 [Pulse Train
Input], the drive inputs the frequency reference received from terminal RP.
1 : PID Feedback Value
The drive inputs the PID control feedback value received from terminal RP.
658
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
Figure 12.100 Pulse Train Input Block Diagram
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for pulse train input terminal RP.
Description
Description
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
0044H (U1-05)
(0000H - FFFFH)
Default
(Range)
0045H (U1-06)
(0000H - FFFFH)
Default
(Range)
0042H (U1-03)
(0000H - FFFFH)
Default
(Range)
0049H (U1-10)
(0000H - FFFFH)
Default
(Range)
0
(0 - 3)