YASKAWA CIPR-GA50C series Technical Manual page 463

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

User Parameter No.
A2-11
A2-12
A2-13
2 : Conveyor
The drive automatically sets the parameters in
No.
A1-02
C1-01
C1-02
C6-01
L3-04
The drive saves the parameters in
Table 12.7 Parameters Saved as User Parameters with the Conveyor Preset
User Parameter No.
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A2-07
3 : Exhaust Fan
The drive automatically sets the parameters in
No.
A1-02
b1-04
C6-01
E1-03
E1-07
E1-08
L2-01
L3-04
The drive saves the parameters in
Table 12.9 Parameters Saved as User Parameters with the Exhaust Fan Preset
User Parameter No.
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A2-07
YASKAWA SIEPC71061753A GA500 Technical Manual
Parameter No. Saved
Table 12.6
Table 12.6 Best Parameter Settings for Conveyor Applications
Control Method Selection
Acceleration Time 1
Deceleration Time 1
Normal / Heavy Duty Selection
Stall Prevention during Decel
Table 12.7
as User Parameters.
Parameter No. Saved
Table 12.8
Table 12.8 Best Parameter Settings for Exhaust Fan Applications
Control Method Selection
Reverse Operation Selection
Normal / Heavy Duty Selection
V/f Pattern Selection
Mid Point A Frequency
Mid Point A Voltage
Power Loss Ride Through Select
Stall Prevention during Decel
Table 12.9
as User Parameters.
Parameter No. Saved
12.2 A: Initialization Parameters
H1-06
H1-07
L5-01
for a conveyor application.
Name
A1-02
b1-01
b1-02
C1-01
C1-02
E2-01
L3-04
for an exhaust fan application.
Name
b1-01
b1-02
b1-04
b3-01
C1-01
C1-02
E1-03
Name
Terminal S6 Function Selection
Terminal S7 Function Selection
Number of Auto-Restart Attempts
Optimal Value
0: V/f Control
3.0 s
3.0 s
0: Heavy Duty Rating
1: General Purpose
Name
Control Method Selection
Frequency Reference Selection 1
Run Command Selection 1
Acceleration Time 1
Deceleration Time 1
Motor Rated Current (FLA)
Stall Prevention during Decel
Optimal Value
0: V/f Control
1: Reverse Disabled
1: Normal Duty Rating
F: Custom
30.0 Hz
50.0 V
1: Enabled for L2-02 Time
1: General Purpose
Name
Frequency Reference Selection 1
Run Command Selection 1
Reverse Operation Selection
Speed Search at Start Selection
Acceleration Time 1
Deceleration Time 1
V/f Pattern Selection
12
463