12.3 b: Application
b5-56: PID Feedback Monitor Gain
No.
Name
(Hex.)
b5-56
PID Feedback Monitor
Gain
(0BE2)
b5-57: PID Feedback Monitor Bias
No.
Name
(Hex.)
b5-57
PID Feedback Monitor Bias
(11DD)
b5-58 to b5-60: PID Setpoints 2 to 4
No.
Name
(Hex.)
b5-58 to b5-60:
PID Setpoints 2 to 4
(1182 - 1184)
RUN
Table 12.34
shows how the different MFDI H1-xx values (3E and 3F) have an effect on the PID setpoint value.
H1-xx = 3E
OFF
ON
OFF
ON
b5-61: PID Trim Mode Lower Limit Sel
No.
Name
(Hex.)
b5-61
PID Trim Mode Lower
Limit Sel
(119A)
0 : Disabled
Does not adjust the PID output with the frequency reference.
1 : Enabled
Adjusts the PID output in relation to the frequency reference. The setting value of b5-62 [PID Trim Mode Lower
Limit Value] sets the lower limit of the post-adjustment value. The maximum output frequency sets the upper
limit.
Note:
• Set b5-01 = 3, 4, 7, or 8 to enable this parameter.
• When b5-61 = 1, you can use this formula to adjust PID output proportional to the frequency reference:
U5-03 [PID Output], Fref [Frequency Reference], and Fmax [Maximum Output Frequency]
*1
Lower limit = b5-62, Upper limit = Maximum output frequency
b5-62: PID Trim Mode Lower Limit Value
No.
Name
(Hex.)
b5-62
PID Trim Mode Lower
Limit Value
(119B)
Note:
Set b5-01 = 3, 4, 7, or 8 to enable this parameter.
512
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the gain for the monitor set in b5-55 [PID Feedback Monitor Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bias for the monitor specified in b5-55 [PID Feedback Monitor Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the PID setpoint when H1-xx = 3E or 3F [MFDI Function Selection = PID Setpoint
Selection 1/2]. This value is a percentage of the maximum output frequency.
Table 12.34 Switching of MFDI and PID Setpoint Value
H1-xx = 3F
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that adjusts the PID output in relation to the frequency reference.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the PID Trim Mode Lower Limit Value as a percentage of the maximum output frequency.
Description
Description
Description
OFF
OFF
ON
ON
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
1.00
(0.00 - 10.00)
Default
(Range)
0.00
(-10.00 - +10.00)
Default
(Range)
0.00%
(0.00 - 100.00%)
PID Setpoint Value
No switch
b5-58 [PID Setpoint2]
b5-59 [PID Setpoint3]
b5-60 [PID Setpoint4]
Default
(Range)
0
(0, 1)
Default
(Range)
0.00%
(0.00 - 100.00%)