12.8 H: Terminal Function Selection
ON : The DC bus voltage is less than the setting value of L2-05.
OFF : The DC bus voltage is more than the setting value of L2-05.
8: During Baseblock (N.O.)
Setting Value
Function
8
During Baseblock (N.O.)
ON : During baseblock
OFF : The drive is not in baseblock.
9: Frequency Reference from Keypad
Setting Value
Function
9
Frequency Reference from
Keypad
ON : The keypad is the frequency reference source.
OFF : b1-01 or b1-15 [Frequency Reference Selection 1 or 2] is the frequency reference source.
A: Run Command from Keypad
Setting Value
Function
A
Run Command Source
ON : The keypad is the Run command source.
OFF : b1-02 or b1-16 [Run Command Selection 1 or 2] is the Run command source.
B: Torque Detection 1 (N.O.)
Setting Value
Function
B
Torque Detection 1 (N.O.)
ON : The output current/torque is more than the torque value set with L6-02 [Torque Detection
Level 1], or the level is less than the torque value set with L6-02 for longer than the time set with
L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-02 for longer than the time
set in L6-03.
• Refer to "L6: Torque Detection" for more information.
C: Frequency Reference Loss
Setting Value
Function
C
Frequency Reference Loss
Note:
Refer to "L4-05: Fref Loss Detection Selection" for more information.
D: Braking Resistor Fault
Setting Value
Function
D
Braking Resistor Fault
E: Fault
Setting Value
Function
E
Fault
632
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal turns on during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Shows the selected frequency reference source.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Shows the selected Run command source.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects overtorque or undertorque.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the drive detects a loss of frequency reference.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects a fault.
Description
Description
Description
Description
Description
Description
Description