12.8 H: Terminal Function Selection
H7-32: Virtual Analog Input Bias
No.
Name
(Hex.)
H7-32
Virtual Analog Input Bias
(1179)
RUN
Expert
H7-40: Virtual Analog Out Signal Select
No.
Name
(Hex.)
H7-40
Virtual Analog Out Signal
Select
(1163)
0 : 0 to 100% (Absolute Value)
1 : -100 to 100%
2 : 0 to 100% (Lower Limit at 0)
H7-41: Virtual Analog Output Function
No.
Name
(Hex.)
H7-41
Virtual Analog Output
Function
(1164)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H7-41 = 102 to monitor U1-02 [Output Frequency].
H7-42: Virtual Analog Output FilterTime
No.
Name
(Hex.)
H7-42
Virtual Analog Output
FilterTime
(1165)
664
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the virtual analog input bias.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the signal level of the virtual analog output.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the monitor to be output from the virtual analog output.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time constant for a primary filter of the virtual analog output.
Description
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
0.0%
(-999.9 - 999.9%)
Default
(Range)
0
(0 - 2)
Default
(Range)
102
(0 - 999)
Default
(Range)
0.00 s
(0.00 - 2.00 s)