H2: Digital Outputs - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.10 H: Terminal Functions
Setting Value
Function
9F
DWEZ Disable
101 to 19F
Inverse Input of 1 to 9F

H2: Digital Outputs

No.
Name
(Hex.)
H2-01
Term MA/MB-MC
Function Selection
(040B)
H2-02
Term P1-C1 Function
Selection
(040C)
H2-03
Term P2-C2 Function
Selection
(040D)
H2-06
Watt Hour Output Unit
Selection
(0437)
H2-07
Modbus Register 1
Address Select
(0B3A)
H2-08
Modbus Register 1 Bit
Select
(0B3B)
H2-09
Modbus Register 2
Address Select
(0B3C)
H2-10
Modbus Register 2 Bit
Select
(0B3D)
H2-20
Comparator 1 Monitor
Selection
(1540)
H2-21
Comparator 1 Lower
Limit
(1541)
H2-22
Comparator 1 Upper
Limit
(1542)
H2-23
Comparator 1 Hysteresis
(1543)
H2-24
Comparator 1 On-Delay
Time
(1544)
H2-25
Comparator 1 Off-Delay
Time
(1545)
H2-26
Comparator 2 Monitor
Selection
(1546)
374
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the DriveWorksEZ program saved in the drive.
ON : No
OFF : Yes
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to enable this function.
Sets the function of the selected MFDI to operate inversely. To select the function, enter "1xx", where the "xx" is
the function setting value.
Note:
You cannot use inverse input for all functions. Refer to
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function set for MFDO terminal MA-MC or MB-MC.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function for MFDO terminal P1-C1.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFDO terminal P2-C2.
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in
through mode.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function
Selection = Watt Hour Pulse Output].
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the monitor number for comparator 1. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-20 = 102 to monitor U1-02 [Output Frequency].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the lower limit detection level for comparator 1 when the full scale analog output
for the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the upper limit detection level for comparator 1 when the full scale analog output
for the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output
for the monitor selected in H2-20 [Comparator 1 Monitor Selection].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the on-delay time for comparator 1.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the off-delay time for comparator 1.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For
example, set H2-26 = 103 to monitor U1-03 [Output Current].
Description
Table 12.55
for more information.
YASKAWA SIEPC71061753A GA500 Technical Manual
Ref.
619
620
Default
Ref.
(Range)
E
622
(0 - 1FF)
0
622
(0 - 1FF)
2
622
(0 - 1FF)
0
622
(0 - 4)
0001
623
(0001 - 1FFF)
0000
623
(0000 - FFFF)
0001
623
(0001 - 1FFF)
0000
623
(0000 - FFFF)
102
624
(000 - 999)
0.0%
624
(0.0 - 300.0%)
0.0%
624
(0.0 - 300.0%)
0.0%
624
(0.0 - 10.0%)
0.0 s
624
(0.0 - 600.0 s)
0.0 s
624
(0.0 - 600.0 s)
103
625
(000 - 999)