YASKAWA CIPR-GA50C series Technical Manual page 539

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

Set C6-03 [Carrier Frequency Upper Limit], C6-04, and C6-05 [Carrier Freq Proportional Gain] to make the
carrier frequency change linearly with the output frequency.
Note:
The drive detects oPE11 [Carrier Frequency Setting Error] when these conditions are correct at the same time:
• C6-04 ≥ C6-03
• C6-05 ≥ 6
C6-05: Carrier Freq Proportional Gain
No.
Name
(Hex.)
C6-05
Carrier Freq Proportional
Gain
(0227)
Set C6-03 [Carrier Frequency Upper Limit], C6-04 [Carrier Frequency Lower Limit], and C6-05 to make the
carrier frequency change linearly with the output frequency.
C6-09: Carrier Freq at Rotational Tune
No.
Name
(Hex.)
C6-09
Carrier Freq at Rotational
Tune
(022B)
If C6-09 = 0 and you do Auto-Tuning on a high frequency motor or low impedance motor, it can cause oC
[Overcurrent]. To prevent oC, increase the carrier frequency value, set C6-09 = 1, then do Auto-Tuning.
The procedure to set the carrier frequency when the A1-02 [Control Method Selection] setting changes.
• When A1-02 = 2 [OLV], set C6-02 = F [Carrier Frequency Selection = User Defined (C6-03 to C6-05)] and
then increase the value set to C6-03 [Carrier Frequency Upper Limit].
• When A1-02 = 5 or 6 [OLV/PM or AOLV/PM], use C6-02 to increase the carrier frequency.
0 : 5 kHz
Note:
When A1-02 = 5 or 6, the carrier frequency is 2 kHz.
1 : Use C6-03
Note:
When A1-02 = 5 or 6, the carrier frequency is the value set to C6-02.
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency Selection
= User Defined (C6-03 to C6-05)] to set this parameter.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
Description
Description
12.4 C: Tuning
Default
(Range)
Determined by C6-02
(0 - 99)
Default
(Range)
0
(0, 1)
12
539