12.8 H: Terminal Function Selection
Figure 12.92 Acceleration/Deceleration Time Gain through Analog Input
6: DC Injection Braking Current
Setting Value
Function
6
DC Injection Braking
Current
Note:
When you set this function, it will disable the setting value of b2-02 [DC Injection Braking Current].
7: Torque Detection Level
Setting Value
Function
7
Torque Detection Level
When A1-02 = 0, 5 [Control Method Selection = V/f, OLV/PM], the drive rated current is 100%. When A1-02 = 2,
6, 8 [OLV, AOLV/PM, or EZOLV], the motor rated current is 100%.
Note:
Use this function with L6-01 [Torque Detection Selection 1]. This parameter functions as an alternative to L6-02 [Torque Detection
Level 1].
8: Stall Prevent Level during Run
Setting Value
Function
8
Stall Prevent Level during
Run
Note:
The drive will use the smaller value of these values for Stall Prevent Level during Run:
• Multi-function analog input terminal analog input value
• L3-06 [Stall Prevent Level during Run]
648
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.
Figure 12.93 DC Injection Braking Current through Analog Input
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters a signal to adjust the overtorque/undertorque detection level.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Description
Description
Description