YASKAWA CIPR-GA50C series Technical Manual page 655

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

H5-03: Communication Parity Selection
No.
Name
(Hex.)
H5-03
Communication Parity
Selection
(0427)
Note:
Restart the drive after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
H5-04: Communication Error Stop Method
No.
Name
(Hex.)
H5-04
Communication Error Stop
Method
(0428)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for Fault [H2-01 to H2-03 =
E] activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. The output terminal set for Fault
[H2-01 to H2-03 = E] activates.
3 : Alarm Only
The keypad shows CE and the drive continues operation. The output terminal set for Alarm [H2-01 to H2-03 =
10] activates.
H5-05: Comm Fault Detection Selection
No.
Name
(Hex.)
H5-05
Comm Fault Detection
Selection
(0429)
If the drive does not receive data from the master during the time set in H5-09 [CE Detection Time], it will detect
a CE error.
0 : Disabled
Does not detect CE. The drive continues operation.
1 : Enabled
Detects CE. If the drive detects CE, it will operate as specified by the setting of H5-04 [Communication Error
Stop Method].
H5-06: Drive Transmit Wait Time
No.
Name
(Hex.)
H5-06
Drive Transmit Wait Time
(042A)
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the communications parity used for MEMOBUS/Modbus communications.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the motor Stopping Method when the drive detects CE [MEMOBUS/Modbus Communication
Err] issues.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that detects CE [Modbus Communication Error] issues during MEMOBUS/
Modbus communications.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time to wait to send a response message after the drive receives a command message
from the master.
12.8 H: Terminal Function Selection
Description
Description
Description
Description
Default
(Range)
0
(0 - 2)
Default
(Range)
3
(0 - 3)
Default
(Range)
1
(0, 1)
Default
(Range)
5 ms
(0 - 65 ms)
12