12.7 F: Options
F6-01: Communication Error Selection
No.
Name
(Hex.)
F6-01
Communication Error
Selection
(03A2)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for Fault [H2-01 to H2-03 =
E] activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. The output terminal set for Fault
[H2-01 to H2-03 = E] activates.
3 : Alarm Only
The keypad shows bUS and the drive continues operation at the current frequency reference.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set to Alarm [H2-01 to H2-03 = 10] activates.
4 : Alarm (Run at d1-04)
The keypad shows bUS and the drive continues operation at the speed set in d1-04 [Reference 4].
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
5 : Alarm - Ramp Stop
The drive stops the motor during the deceleration time set in C1-02 [Deceleration Time 1].
After you remove the bUS alarm, the motor will accelerate to the previous frequency reference.
F6-02: Comm External Fault (EF0) Detect
No.
Name
(Hex.)
F6-02
Comm External Fault (EF0)
Detect
(03A3)
0 : Always Detected
1 : Detected during RUN Only
F6-03: Comm External Fault (EF0) Select
No.
Name
(Hex.)
F6-03
Comm External Fault (EF0)
Select
(03A4)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. The output terminal set for Fault [H2-01 to H2-03 =
E] activates.
1 : Coast to Stop
The output turns off and the motor coasts to stop. The output terminal set for Fault [H2-01 to H2-03 = E]
activates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. The output terminal set for Fault
[H2-01 to H2-03 = E] activates.
3 : Alarm Only
584
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the method to stop the motor or let the motor continue operating when the drive detects bUS
[Option Communication Error].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the conditions at which EF0 [Option Card External Fault] is detected.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the method to stop the motor or let the motor continue operating when the drive detects EF0
[Option Card External Fault].
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Default
(Range)
1
(0 - 5)
Default
(Range)
0
(0, 1)
Default
(Range)
1
(0 - 3)