A: Initialization Parameters; A1: Initialization - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.4

A: Initialization Parameters

A1: Initialization

No.
Name
(Hex.)
A1-00
Language Selection
(0100)
RUN
A1-01
Access Level Selection
(0101)
RUN
A1-02
Control Method
Selection
(0102)
A1-03
Initialize Parameters
(0103)
A1-04
Password
(0104)
A1-05
Password Setting
(0105)
A1-06
Application Preset
(0127)
A1-07
DriveWorksEZ Function
Selection
(0128)
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the language for the LCD keypad.
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will
not reset this parameter.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets user access to parameters. The access level controls which parameters the keypad
will display, and which parameters the user can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the control method for the drive application and the motor.
0 : V/f Control
2 : Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
8 : EZ Vector Control
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Entry point for the password set in A1-05 [Password Setting]. The user can view the
settings of parameters that are locked without entering the password. Enter the correct
password in this parameter to change parameter settings.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Set the password to lock parameters and prevent changes to parameter settings. Enter
the correct password in A1-04 [Password] to unlock parameters and accept changes.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive to operate in selected application conditions.
0 : General-purpose
1 : Water Supply Pump 2
2 : Conveyor
3 : Exhaust Fan
4 : HVAC Fan
5 : Air Compressor
6 : Crane (Hoist)
7 : Crane (Traveling)
8 : Conveyor 2
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the drive to operate with DriveWorksEZ.
0 : DWEZ Disabled
1 : DWEZ Enabled
2 : Enabled/Disabled wDigital Input

11.4 A: Initialization Parameters

Default
(Range)
0
(0 - 12)
2
(0 - 3)
0
(0, 2, 5, 6, 8)
0
(0 - 3330)
0000
(0000 - 9999)
0000
(0000 - 9999)
0
(0 - 8)
0
(0 - 2)
Ref.
457
457
458
459
460
460
461
473
11
337

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents