b5-63: PID Differential FB Monitor Sel
No.
Name
(Hex.)
b5-63
PID Differential FB
Monitor Sel
(119C)
Note:
• You cannot select parameter U5-xx.
• This parameter is disabled when set to 000.
b5-64: PID Differential FB Monitor Gain
No.
Name
(Hex.)
b5-64
PID Differential FB
Monitor Gain
(119D)
b5-65: PID Differential FB Monitor Bias
No.
Name
(Hex.)
b5-65
PID Differential FB
Monitor Bias
(119F)
b5-66: PID Feedback Monitor Level
No.
Name
(Hex.)
b5-66
PID Feedback Monitor
Level
(11DE)
0 : Absolute
1 : Bi-directional (+/-)
b5-67: PID Differential FB Monitor Lvl
No.
Name
(Hex.)
b5-67
PID Differential FB
Monitor Lvl
(11DF)
0 : Absolute
1 : Bi-directional (+/-)
b5-89: Sleep Method Selection
No.
Name
(Hex.)
b5-89
Sleep Method Selection
(0B89)
RUN
0 : Standard
1 : EZ Sleep/Wake-up
b5-90: EZ Sleep Unit
No.
Name
(Hex.)
b5-90
EZ Sleep Unit
(0B90)
0 : 0.1Hz units
1 : rev/min
YASKAWA SIEPC71061753A GA500 Technical Manual
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Selects the monitor (Ux-xx) used as the PID Differential Feedback. Set the x-xx part of the Ux-xx
[Monitor].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the bias for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the signal level for the monitor specified in b5-55 [PID Feedback Monitor Selection].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the signal level for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets sleep and wake up operation when using PID.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed] and b5-92 [EZ Sleep Level].
Description
Description
Description
Description
Description
Description
Description
12.3 b: Application
Default
(Range)
000
(000 - 999)
Default
(Range)
1.00
(0.00 - 10.00)
Default
(Range)
0.00
(-10.00 - +10.00)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
12
513