Do An Actual-Load Test Run - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

4.10 Test Run
• Make sure that the motor is fully stopped.
• Connect the motor with the machine.
Make sure that there are no loose installation screws and that the motor load shafts and machine junctions are
correctly secured.
• Keep the keypad near you to push
Items to Check before Operation
• Make sure that the direction of the machine operation is correct (The motor must rotate in the correct direction).
• Make sure that the motor accelerates and decelerates smoothly.

Do an Actual-Load Test Run

Before a test run, make sure that U1-03 [Output Current] is not too high.
Connect the motor and machine, then do the test run with the same procedure that you used for the no-load test
run.
1.
Energize the drive, or push
2.
Use
/
3.
Push
to illuminate the LOCAL/REMOTE LED.
4.
Push
.
The RUN indicator illuminates, and the motor runs at 6.00 Hz in the forward direction.
5.
Make sure that the motor is rotating in the correct direction and that the drive does not show a fault.
If the drive detects a fault, remove the cause.
6.
Push
to increase the frequency reference value.
Change the setting value in increments of 10 Hz if necessary and examine the response.
Ex.: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz
7.
Each time you increase the setting value, use U1-03 [Output Current] to check the drive output current.
When the output current of the drive is not more than the motor rated current, the status is correct.
8.
Make sure that the motor rotates correctly, then push
The RUN LED flashes and goes off when the motor stops completely.
9.
Change the frequency reference and direction of motor rotation, and make sure that there are no unusual
sounds or vibrations.
10.
If the control function causes hunting or oscillation errors, adjust the settings to stop the errors.
142
immediately if there is unusual or incorrect operation.
to show the frequency reference screen.
/
/
to set d1-01 = 6.00 [Frequency Reference 1 = 6.00 Hz], then push
.
YASKAWA SIEPC71061753A GA500 Technical Manual
.