B: Application; B1: Operation Mode Selection - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.5

b: Application

b1: Operation Mode Selection

No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
b1-02
Run Command Selection
1
(0181)
b1-03
Stopping Method
Selection
(0182)
b1-04
Reverse Operation
Selection
(0183)
b1-06
Digital Input Reading
(0185)
b1-07
LOCAL/REMOTE Run
Selection
(0186)
b1-08
Run Command Select in
PRG Mode
(0187)
b1-14
Phase Order Selection
(01C3)
b1-15
Frequency Reference
Selection 2
(01C4)
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
Note:
When A1-02 = 5, 6, 8 [Control Method Selection = OLV/PM, AOLV/PM, EZOLV],
the setting range is 0, 1, 3.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
9 : Stop with Constant Distance
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the reverse operation function. Disable reverse operation in fan or pump
applications where reverse rotation is dangerous.
0 : Reverse Enabled
1 : Reverse Disabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the number of times that the drive reads the sequence input command to prevent
malfunction because of noise.
0 : Single Scan
1 : Double Scan
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets drive response to an existing Run command when the drive receives a second Run
command from a different location.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the conditions for the drive to accept a Run command entered from an external
source when using the keypad to set parameters.
0 : Disregard RUN while Programming
1 : Accept RUN while Programming
2 : Allow Programming Only at Stop
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can
align the Forward Run command from the drive and the forward direction of the motor
without changing wiring.
0 : Standard
1 : Switch Phase Order
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the input method for frequency reference 2.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input

11.5 b: Application

Default
Ref.
(Setting Range)
1
476
(0 - 4)
1
478
(0 - 3)
0
478
(0 - 3, 9)
0
481
(0, 1)
1
482
(0, 1)
0
482
(0, 1)
0
482
(0 - 2)
0
483
(0, 1)
0
483
(0 - 4)
339
11