YASKAWA CIPR-GA50C series Technical Manual page 172

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

5.2 European Standards
A - Braided shield cable
B - Metal plate
A - Grounding surface (Remove any
paint or sealant.)
B - Enclosure panel
C - Metal plate
D - Drive
E - Shielded wire
5.
Connect an AC reactor or DC reactor to decrease harmonic distortion. Refer to
to select a DC reactor.
Note:
• To maintain compliance with EN 61000-3-2 on drive models 2001 to 2006, 4001 to 4004, install a DC reactor.
Ground Wiring
WARNING! Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.
WARNING! Electrical Shock Hazard. Ground the neutral point on the power supply of drive models 2xxxE, BxxxE, and 4xxxE to
comply with the EMC Directive before you turn on the EMC filter or if there is high resistance grounding. If the EMC filter is
switched ON without the neutral point being grounded or if there is high resistance grounding, it can cause death or serious
injury.
172
Figure 5.5 Ground the shield
Figure 5.6 Install a Drive with a Built-in EMC Filter
C - Cable clamp (conductive)
F - Motor
G - Motor cable
H - Cable clamp
I - Grounding wire
YASKAWA SIEPC71061753A GA500 Technical Manual
DC Reactors on page 178