7.4 Faults
Code
Name
Note:
• The drive detects this fault if the electronic thermal protector of the drive started the motor overload protection.
• Do a Fault Reset to clear the fault.
• L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.
Code
Name
oL2
Drive Overload
Note:
• The drive detects this fault if the electronic thermal protector of the drive started the drive overload protection.
• Do a Fault Reset to clear the fault.
• L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.
Code
Name
oL3
Overtorque Detection 1
Note:
• The drive detects this fault if the drive output current is more than the level set in L6-02 for longer than L6-03.
• Do a Fault Reset to clear the fault.
• If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in L6-01 [Torque Detection Selection 1].
• L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.
254
Causes
There is increased motor loss from overexcitation
operation.
The speed search-related parameters are set
incorrectly.
Phase loss in the input power supply is causing the
output current to change.
The motor main circuit cable is too long.
Causes
The load is too large.
The acceleration/deceleration times or cycle times
are too short.
The V/f pattern does not fit the motor qualities.
The drive capacity is too small.
Overload occurred while running at low speed.
The torque compensation gain is too large.
The speed search-related parameters are set
incorrectly.
Phase loss in the input power supply is causing the
output current to change.
Overload occurred during overexcitation
deceleration.
Causes
A fault occurred on the machine.
Example: The machine is locked.
The parameters are incorrect for the load.
Possible Solutions
• Lower the value set in n3-13 [OverexcitationBraking (OEB)
Gain].
• Set L3-04 ≠ 4 [Stall Prevention during Decel ≠ Overexcitation/
High Flux].
• Set n3-23 = 0 [Overexcitation Braking Operation = Disabled].
• Examine the settings for all speed search related parameters.
• Adjust b3-03 [Speed Search Deceleration Time].
• Set b3-24 = 1 [Speed Search Method Selection = Speed
Estimation] after Auto-Tuning.
Make sure that there is no phase loss, and repair problems.
• Replace the drive with a larger capacity model.
• Decrease C6-02 [Carrier Frequency]. Or set C6-02 = B.
Possible Solutions
Decrease the load.
• Examine the acceleration/deceleration times and the motor
start/stop frequencies (cycle times).
• Increase the values set in C1-01 to C1-08 [Acceleration/
Deceleration Times].
• Examine the ratios between the V/f pattern frequency and
voltage. Decrease the voltage if it is too high compared to the
frequency.
• Adjust E1-04 to E1-10 [V/f Pattern Parameters]. Decrease the
values set in E1-08 [Mid Point A Voltage] and E1-10
[Minimum Output Voltage]. For motor 2, adjust E3-04 to E3-
10.
Note:
If the values set in E1-08 and E1-10 are too low, the overload
tolerance will decrease at low speeds.
Replace the drive with a larger capacity model.
• Decrease the load when running at low speed.
• Replace the drive with a larger capacity model.
• Decrease the value set in C6-02 [Carrier Frequency
Selection].
Decrease the value set in C4-01 [Torque Compensation Gain] to
make sure that the motor does not stall.
• Examine the settings for all speed search-related parameters.
• Adjust b3-03 [Speed Search Deceleration Time].
• Set b3-24 = 1 [Speed Search Method Selection = Speed
Estimation] after Auto-Tuning.
• Correct errors with the wiring for main circuit drive input
power.
• Make sure that there is no phase loss, and repair problems.
• Decrease the value set in n3-13 [OverexcitationBraking (OEB)
Gain].
• Decrease the value set in n3-21 [HSB Current Suppression
Level].
Possible Solutions
Examine the machine and remove the cause of the fault.
Adjust L6-02 [Torque Detection Level 1] and L6-03 [Torque
Detection Time 1] settings.