EMC Directive
Use drives with built-in EMC filters or install external EMC filters to the drive input side to comply with the
EMC Directive.
Drives with built-in EMC filters (models 2xxxE, BxxxE, 4xxxE) were tested in accordance with European
standard EN 61800-3:2004/A1:2012, and comply with the EMC Directive.
■
Install a Drive to Conform to the EMC Directive
Install drive models 2xxxE, BxxxE, and 4xxxE with this procedure to comply with the EMC Directive when the
drive is a single unit or installed in a larger device.
1.
Install the drive on a grounded metal plate.
2.
Wire the drive and motor.
3.
Ground the wire shielding on the drive side and motor side.
A - Drive
B - Wiring length
C - Motor
*1
The maximum wiring length between the drive and motor is:
• 2xxxE, 4xxxE: 20 m (65.6 ft)
• BxxxE: 10 m (32.8 ft)
Note:
• Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
• Keep the cable between the drive and motor and the grounding wire as short as possible.
4.
Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications or local safety standards.
YASKAWA SIEPC71061753A GA500 Technical Manual
Table 5.7 Recommended Fuse: Three-Phase 400 V Class
Fuse
Manufacturer: Bussmann
Model
FWH-40B
FWH-40B
FWH-50B
FWH-70B
FWH-70B
FWH-90B
FWH-90B
*1
Figure 5.4 Wiring the Drive and Motor
Drive Model
4018
4023
4031
4038
4044
4060
D - Metal conduit
E - Grounding wire
5.2 European Standards
Fuse
Manufacturer: Bussmann
Model
FWH-80B
FWH-100B
FWH-125B
FWH-175B
FWH-200B
FWH-200B