Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4060
-, +1, +2
B1, B2
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use these closed-loop crimp
terminals or equivalent to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
• 8-4NS from JST Mfg. Co., Ltd.
• R8-4S from NICHIFU Co.,Ltd.
Connect a Fuse to the Input Side (Primary Side)
The drive circuit protection must comply with EN 61800-5-1:2007 for protection against a short circuit in the
internal circuitry. Connect semiconductor protection fuses on the input side for branch circuit protection.
Refer to
Single-Phase 200 V Class on page
Class on page 170
for more information about recommended fuses.
WARNING! Electrical Shock Hazard. After the drive blows a fuse or trips an RCM/RCD, do not immediately energize the drive
or operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators
are OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of
the problem, contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you
operate the drive or peripheral devices, it can cause serious injury or death.
Three-Phase 200 V Class
Table 5.2 Factory-Recommended Branch Circuit Protection: Three-Phase 200 V Class
Drive Model
2001
2002
2004
2006
2010
2012
Single-Phase 200 V Class
Table 5.3 Factory-Recommended Branch Circuit Protection: Single-Phase 200 V Class
Drive Model
B001
B002
B004
B006
YASKAWA SIEPC71061753A GA500 Technical Manual
Recommended
Applicable Gauge
Gauge
2
mm
mm
2
25
6 - 35
16
4 - 25
25
6 - 35
10
2.5 - 16
10
6 - 16
169,
Three-Phase 200 V Class on page
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
FWH-25A14F
FWH-25A14F
FWH-25A14F
FWH-25A14F
FWH-70B
FWH-70B
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
FWH-25A14F
FWH-25A14F
FWH-60B
FWH-80B
5.2 European Standards
Wire
Terminal Screw
Stripping
*1
Length
Size
Shape
mm
18
M5
18
M5
18
M5
10
M4
-
M6
169, and
Drive Model
2021
2030
2042
2056
2070
2082
Drive Model
B010
B012
B018
Tightening Torque
N∙m (in∙lb)
• ≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
2.3 - 2.5
(19.8 - 22)
• ≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
2
(copper wire).
Three-Phase 400 V
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
FWH-90B
FWH-100B
FWH-150B
FWH-200B
FWH-200B
FWH-225A
Semiconductor Protection Fuse
Rated Current
Manufacturer: EATON/Bussmann
FWH-100B
FWH-125B
FWH-150B
169