12.8 H: Terminal Function Selection
76: Down 2 Command
Setting Value
Function
76
Down 2 Command
When you activate the terminal set for Up2 Command, the bias will increase. When you activate the terminal set
for Down 2 Command, the bias will decrease. When you activate or deactivate the two commands, the drive will
hold the frequency reference.
Note:
• When using this function, set the optimal bias limit value with d4-08 and d4-09 [Up/Down 2 Bias Upper Limit/Lower Limit].
• Refer to "d4: Frequency Ref Up/Down & Hold" for more information.
77: ASR Gain (C5-03) Select
Setting Value
Function
77
ASR Gain (C5-03) Select
ON : C5-03
Switches the proportional gain to C5-03 [ASR Proportional Gain 2].
OFF : C5-01
Switches the proportional gain to C5-01 [ASR Proportional Gain 1].
Note:
Refer to "C5: Automatic Speed Regulator (ASR)" for more information.
7A: KEB Ride-Thru 2 Activate (N.C.)
Setting Value
Function
7A
KEB Ride-Thru 2 Activate
(N.C.)
ON : Normal operation
OFF : Deceleration during momentary power loss
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The L2-29
[KEB Method Selection] setting will not have an effect.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 65, 66] and KEB Ride-Thru 2 [H1-xx = 7A, 7B] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
• Refer to "KEB Ride-Thru function" for more information.
7B: KEB Ride-Thru 2 Activate (N.O.)
Setting Value
Function
7B
KEB Ride-Thru 2 Activate
(N.O.)
ON : Deceleration during momentary power loss
OFF : Normal operation
When KEB Ride-Thru 2 is input, the drive will use Single Drive KEB Ride-Thru 2 for KEB operation. The L2-29
[KEB Method Selection] setting will not have an effect.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 65, 66] and KEB Ride-Thru 2 [H1-xx = 7A, 7B] at the same time, the drive will detect oPE03
[Multi-Function Input Setting Err].
• Refer to "KEB Ride-Thru function" for more information.
7C: Short Circuit Braking (N.O.)
Setting Value
Function
7C
Short Circuit Braking
(N.O.)
618
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to decrease the frequency reference bias value to decelerate the motor when the terminal is activated. Set this
function and H1-xx = 75 [Up 2 Command] at the same time.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to switch the ASR proportional gain set in C5-01 [ASR Proportional Gain 1] and C5-03 [ASR Proportional
Gain 2].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation of Short Circuit Braking (N.O.).
Description
Description
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents