4.4 Drive Mode and Programming Mode

Change Parameter Settings

Show the frequency reference screen in advance.
Note:
Push and hold
to go back to the frequency reference screen from any screen.
Use these steps to change C1-01 [Acceleration Time 1] from 1.0 s (default) to 2.0 s.

Verify and Set the Changed Parameters (Verify Menu)

Show the frequency reference screen in advance.
Note:
Push and hold
to go back to the frequency reference screen from any screen.
Use Verify mode to view all parameters that are not at default settings. This is very useful when you replace a
drive. When there are no changes to parameter settings, the display shows
and re-edit changed parameters.
Note:
The drive will only display A1-02 [Control Method Selection], A1-xx, A2-01 to A2-32 [User Parameter 1 to User Parameter 32], and
E5-01 [PM Motor Code Selection].
120
Figure 4.7 Key operation examples in Setup Mode
Figure 4.8 Key Operation Examples for Parameter Settings
Figure 4.9
shows the procedure.
Figure 4.9 Verify and Set the Changed Parameters
. This lets you quickly access
YASKAWA SIEPC71061753A GA500 Technical Manual