Siemens SINAMICS G150 Manual page 1199

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Tec_ctr mop config
p2230[D] (00100)
Data save active
Initial rounding-off active
Non-volatile data save active
The ramp-function generator is always active
Tec_ctrl mop raise
p2235[C]
(0)
Tec_ctrl Mop lower
p2236[C]
(0)
Tec_ctrl mop max
-200.00...200.00 [%]
p2237[D] (100.00)
Tec_ctrl mop min
-200.00...200.00 [%]
p2238[D] (-100.00)
<1>
For p2230.0 = 0, this setpoint is entered after ON.
<2>
If initial rounding-off is active (p2230.2 = 1), the selected ramp-up/down times are exceeded accordingly.
<101> The pre-assignment of the sampling time in p0115[6] is 4000.00 μs.
1
2
DO: SERVO, VECTOR, VECTOR3P, VECTORMV
Technology controller - Motorized potentiometer (r0108.16 = 1)
0 = The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
1 = The setpoint for the motorized potentiometer is saved after OFF and after ON is entered using r2231.
0 = Without initial rounding.
1 = With initial rounding. The ramp-up/down time set is exceeded accordingly.
0 = Non-volatile data save not activated.
1 = The setpoint for the motorized potentiometer is saved in a non-volatile fashion (for p2230.0 = 1).
0 = Ramp-up encoder inactive with pulse disable.
1 = The ramp-up encoder is calculated independently of the pulse enable.
Old value is kept
0 0
Tec_ctr mop befRFG
0 1
r2245
1 0
1 1
1 = OFF1 enable missing
[2634.0]
3
4
<2>
<2>
Tec_ctr mop t_r-up
Tec_ctr mop t_r-dn
0.0...1000.0 [s]
0.0...1000.0 [s]
p2247[D] (10.0)
p2248[D] (10.0)
y
p2237
x
p2238
y = 0
r0046.0
Tec_ctrl mop start
-200.00...200.00 [%]
Tec_ctrl mop mem
p2240[D] (0.00)
r2231
from setpoint memory
5
6
fp_7954_51_eng.vsd
04.07.13 V04.07.00
p0115[6] (Drive Object)
<101>
Tec_ctr mop aftRFG
y
r2250
t
<1>
7
8
Function diagram
- 7954 -
SINAMICS

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents