B.2 b: Application
B.2 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PI
control, Energy Savings, and a variety of other application-related settings.
u

b1: Operation Mode Selection

No.
(Addr.
Name
Hex)
Frequency Reference
b1-01
Selection for AUTO
(180)
mode
Run Command
b1-02
Selection for AUTO
(181)
mode
b1-03
Stopping Method
(182)
Selection
b1-04
Reverse Operation
(183)
Selection
Run Command
b1-08
Selection in
(187)
Programming Mode
b1-11
Drive Delay Time
(1DF)
Setting
b1-14
Phase Order Selection
(1C3)
b1-17
Run Command at Power
(1C6)
Up
u

b2: DC Injection Braking and Short Circuit Braking

No.
(Addr.
Name
Hex)
b2-01
DC Injection Braking
(189)
Start Frequency
b2-02
DC Injection Braking
(18A)
Current
b2-03
DC Injection Braking
(18B)
Time at Start
b2-04
DC Injection Braking
(18C)
Time at Stop
b2-09
Motor Pre-Heat Current
(1E1)
2
284
LCD Display
Ref Source 1
0: HOA keypad
0: Operator
1: Terminals (Analog Input Terminals)
1: Analog Input
2: Serial communications (APOGEE FLN, BACnet,
2: Serial Com
MEMOBUS/Modbus, or Metasys N2)
3: Option PCB
3: Option card
Run Source 1
1: Control Circuit Terminal
1: Digital Inputs
2: Serial communications (APOGEE FLN, BACnet,
2: Communication
MEMOBUS/Modbus, or Metasys N2)
3: Option PCB
3: Option card
Stopping Method
0: Ramp to stop
0: Ramp to Stop
1: Coast to stop
1: Coast to Stop
2: DC Injection Braking to stop
2: DCInj to Stop
3: Coast with timer
3: Coast w/Timer
Reverse Oper
0: Reverse enabled
0: Reverse Enabled
1: Reverse disabled
1: Reverse Disabled
RUN dur PRG Mode
0: Run command is not accepted while in Programming Mode
0: Run
1: Run command is accepted while in Programming
Disabled@PRG
2: Prohibit entering Programming Mode during Run
1: ModeRun
Enabled@PRG
2: Prg only @ Stop
After a Run command is entered, the drive output waits until
Run Delay Time
this delay time has passed before starting.
Rotation Sel
0: Standard
0: Standard
1: Switch phase order (reverses the direction of the motor)
1: SwitchPhaseOrder
0: Disregarded.
Run Cmd @ Pwr On
A new Run command must be issued after power up.
0: Cycle Ext Run
1: Allowed.
1: Accept Ext Run
Motor will start immediately after power up if a Run command
is already enabled.
LCD Display
Sets the frequency at which DC Injection Braking starts when
"Ramp to stop" (b1-03 = 0) is selected.
DCInj Start Freq
Sets the DC Injection Braking current as a percentage of the
DCInj Current
drive rated current.
Sets DC Injection Braking time at start. Disabled when set to
DCInj Time@Start
0.00 seconds.
Sets DC Injection Braking time at stop.
DCInj Time@Stop
Determines the percentage of motor rated output current used
Preheat Current
for the motor pre-heat function.
Description
Description
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
Values
Page
Default: 1
127
Range: 0 to 3
Default: 1
129
Range: 1 to 3
Default: 1
129
Range: 0 to 3
Default: 1
158
Range: 0, 1
Default: 0
Range: 0 to 2
Default: 0 s
Min.: 0
Max.: 600
Default: 0
158
Range: 0, 1
Default: 1
158
Range: 0, 1
Values
Page
<1>
Default:
158
Min.: 0.0 Hz
Max.: 10.0 Hz
Default: 50%
Min.: 0
159
Max.: 100
Default: 0.00 s
Min.: 0.00
159
Max.: 10.00
Default: 0.00 s
Min.: 0.00
159
Max.: 10.00
Default: 5%
Min.: 0
Max.: 100