5.2 b: Application
Setting 0: Disabled
A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
n
b1-11: Drive Delay Time Setting
If a time is set to b1-11, the drive will delay executing a Run command until the set time has expired. During Drive Delay
Time execution, the digital operator keypad will display "WrUn". Both Alarm and Run indicators will blink while the drive
waits to execute the Run command.
No.
b1-11
n
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No.
b1-14
n
b1-15: Frequency Reference Selection 2
Enabled when H1-oo = 2 and the terminal is closed.
Refer to b1-02: Run Command Selection 1 on page 148
No.
b1-15
n
b1-16: Run Command Selection 2
Enabled when H1-oo = 2 and the terminal is closed.
Refer to b1-01: Frequency Reference Selection 1 on page 147
No.
b1-16
n
b1-17: Run Command at Power Up
Determines whether an external Run command that is active during power up will start the drive.
No.
b1-17
Setting 0: Disregarded
A new Run command must be issued after power up. Cycle the Run command to start the drive.
Note:
For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is issued at
power up, the RUN indicator LED will flash quickly.
Setting 1: Allowed
The motor will start immediately after a power up if a Run command is already enabled.
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin
rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to
powering up the drive. Failure to comply may cause serious injury.
u

b2: DC Injection Braking and Short Circuit Braking

These parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.
152
Parameter Name
Drive Delay Time Setting
Parameter Name
Phase Order Selection
Refer to Setting 2: External Reference 1/2 Selection on page 207
Parameter Name
Frequency Reference Selection 2
Refer to Setting 2: External Reference 1/2 Selection on page 207
Parameter Name
Run Command Selection 2
Parameter Name
Run Command at Power Up
for details.
for details.
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
Setting Range
0 to 600 s
Setting Range
0, 1
Setting Range
0 to 4
Setting Range
0 to 3
Setting Range
0, 1
Default
0
Default
0
and
Default
0
and
Default
0
Default
1