6.10 Troubleshooting without Fault Display
u
Motor Does Not Restart after Power Loss
Cause
The Run command was not issued again when power
was restored.
The relay that is supposed to maintain the Run
command has been switched off.
336
• Check the sequence and wiring that has been set up to enter the Run command.
• A relay should be set up to make sure the Run command remains enabled throughout any power
loss.
Check wiring and circuitry for the relay intended to keep the Run command enabled.
Possible Solutions
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual